background image

12

VAR

Swegon reserves the right to alter specifications. 

20111011 

www.swegon.com

Figure 24. Shows the calibration time diagram.  
A = Calibration no. 
B = Time after energizing (min).

3,52 V

V DC

1

2

8

9

GLB181.1E/3

G G0

YC UC

6

Y1

7

Y2

Figure 25. Shows how to connect a voltmeter for checking the 
true value.

Forcing the commissioning damper to the fully 
closed position:

Fit a jumper on G0 (black cable marked 2) with Y2 
(orange cable marked 7). The actuator should close for a 
maximum period of 150 seconds.

To force the commissioning damper to the fully 
open position:

Fit a jumper on G0 (black cable marked 2) with Y1 (violet 
cable marked 6). This is most easily done by disconnecting 
the grey cable for the control signal marked 9.

To override with the AST setting instrument

The Y signal can also be set from the AST 10 hand-held 
micro terminal. Press Y button and change the signal to 
10 V with the – or + keys on the side of the display. To 
acknowledge by pressing SET. When you disconnect the 
Setting instrument, you also remove the means of overrid-
ing the system. 

The VAR 4 as a constant-flow controller

When the VAR 4 is to be used as a constant flow 
controller,this can be done in two ways . It is appropriate 
to use the min. flow setting as the set point for the con-
stant airflow. 24 V AC only should be connected to the 
cable pair 1 and 2. You can also use the max. airflow set-
ting, however in this case you must make a short circuit 
between 2 and 3, see under Checking the max. airflow.

Important!

The release button on the unit must not be used when the 
unit is energized. If this occurs, the controller will lose its 
positioning capability and you will have to de-energize the 
unit for at least five seconds to remedy the situation. If you 
want to test or force the commissioning damper, use the 
jumper connections shown below or use the AST 10 hand-
held micro terminal. 

Checking the min. flow:

If possible, zero volt is transmitted from the room unit or the 
main control system. If this possibility is lacking, then discon-
nect YC (grey cable, marked 8). Measure the pressure in the 
pressure tapping and calculate the airflow using the K-factor 
for the relevant size. Check also the max. airflow.

Regulating the commissioning damper to max. flow:

If possible, 10 volt is transmitted from the room unit or 
the main control system. If this possibility is lacking, then 
disconnect YC (grey cable, marked 8), fit a jumper on G0 
(black cable marked 2) with Y2 (orange cable marked 7) 
and Y1 (violet cable marked 6).

VAR 4

Checking the performance

Start

After energizing the system, the VAV unit calibrates the 
pressure sensor as illustrated in the diagram below. Each 
calibration takes 90 seconds and the unit is then idle. This 
means that the user should not precision adjust the min. 
and max. airflows with the AST 10 hand-held micro termi-
nal, if required, until after three hours after energizing to 
avoid that the unit is idle too often.  There is no in-opera-
tion indicator that shows that zero calibration is in progress.

To change the settings

The min./max. airflow should be calculated and set as 
follows: 

 
Q

max

 %  required max. airflow (Q

max

) divided by nominal airflow 

(Q

nom

). 

Q

min

  %  required min. airflow (Q

min

) divided by nominal airflow 

(Q

nom

). 

Example: 
VAR, dim. Ø160, required min./max. airflows: 51/119 l/s. 
Q

max 

%   Q

max

 / Q

nom

  =  119/170  = 0.70 = 70% 

Q

min  

%   Q

min

 /  Q

nom 

 =   51/170  = 0.30 = 30% 

Q

nom

  can be read in Table 1 on page 9.

Summary of Contents for BELIMO ZTH-GEN

Page 1: ...ce 20111011 Contents Installation Wiring guides Pages 2 7 Commissioning Flows Pages 7 8 How to use the VAR 1 Pages 9 10 How to use the VAR 2 Pages 10 11 How to use the VAR 4 Pages 12 13 How to use the VAR 5 Page 13 Dimensions and weights Page 14 ...

Page 2: ... mm length of straight duct 2 Sound attenuator with sound baffles Figure 4 Installation demands a length of straight duct A 2 x B 1 VAR Variable flow commissioning damper Figure 2 Variable flow commissioning damper VAR 1 with FSR fixing clamp 2 and sound attenuator 3 If the sound attenuator is equipped with a sound baffle or centre body it should be installed at a distance 2 x the duct diameter ØD...

Page 3: ... airflow Wiring diagrams Figure 8 Wiring diagram for VAR 2 Figure 7 Wiring diagram for VAR 1 Colour codes 1 Black 2 Red 3 and 5 White Insulate any conductors not in use VAR 1 Belimo compact Supply voltage 24 V AC 20 50 60 Hz Supply voltage 24 V DC 10 Controller and motor 6 VA Input 3 resistance 100 kOhm Input 3 control signal 0 10 alt 2 10 V DC Output 5 true value 2 10 V DC max 0 6 mA Ambient air ...

Page 4: ...SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN VAR VAR LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN VAR VAR RTC RTCT Room thermostat Figure 10 The diagram shows how to wire the VART room ther mostat with simultaneous control of the extract air The figure also shows an alternative with RTCT duct temperature sensor 1 VAR Supply air 2 VAR Extract air CO2 and temperature control...

Page 5: ...mo Compact 1 VAR Supply air 2 VAR Extract air Y LMV D3 MP SWN NMV D3 MP SWN LMV D3 MP SWN NMV D3 MP SWN DETECT O VAR VAR Y U U DETECT O VAR VAR Figure 14 Wiring diagram VAR 4 Siemens 1 VAR Supply air 2 VAR Extract air VRD2 Ser Actuator VRD3 Figure 13b Jumper configuration VAR 2 Belimo Universal VRD2 DETECT O controls to fully open damper VRD3 DETECT O controls to preset flow for V max Figure 13a W...

Page 6: ...th VART 5 as master Figure 16 The diagram shows the connections between master slave unit In this wiring configuration the VAR slave controller should be set to a flow range of 0 100 of the nominal airflow 1 VAR Supply air 2 VAR Extract air LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN LMV D3 MP SWN NMV D3 MP SWN VRD3 SWN DETECT O VAR VAR RTC VAV regulation with room thermostat and presence detector 1 VAR ...

Page 7: ...direction should always be such that the damper is fitted down stream of the flow measuring device The unit s rating plate includes air direction arrows Control signals All the electronic VAR devices are designed for a signal range of 0 10V DC Any deviation from this range is indicated on the product rating plate If a direct wired room thermostat is used for controlling the airflow requirements th...

Page 8: ... 5Pa Qnom max 120Pa K factor 1000 x 400 762 3735 341 0 1200 x 400 915 4480 409 0 1400 x 400 1069 5236 478 0 1600 x 400 1221 5981 546 0 500 x 500 479 2344 214 0 600 x 500 575 2815 257 0 700 x 500 671 3286 300 0 800 x 500 767 3757 343 0 1000 x 500 959 4699 429 0 1200 x 500 1149 5631 514 0 1400 x 500 1342 6573 600 0 1600 x 500 1534 7515 686 0 600 x 600 691 3385 309 0 700 x 600 807 3955 361 0 800 x 60...

Page 9: ...r If this is not done you will destroy the output on the control equipment The damper will move to the open position Measure the voltage U and calculate the airflow using Formula 2 on page 7 Figure 21 Shows how to connect a voltmeter for checking the true value Figur 22 ZTH GEN hand held micro terminal VAR 1 as a constant flow controller VAR 1 can be used as a constant flow controller in two ways ...

Page 10: ...u of the VAV controller Start Connect the cable provided to the VAV controller Reply The type of controller connected appears in the display window OK button The serial number of the controller is shown button The program version of the controller is shown Select fun ction Navigate forward backward to scroll between the various menu positions see table below Exit Disconnect the cable to the VAV co...

Page 11: ...s 51 119 l s Qmax Qmax Qnom 119 170 0 70 70 Qmin Qmin Qnom 51 170 0 30 30 Qnom is read from Table 1 on page 9 Enter the settings directly in the controller No external instrument is needed but the settings can also be adjusted with Belimo s instrument ZTH GEN Configuration menu ZTH GEN Start Hold the OK button depressed and at the same time connect to the VAV controller HW Version SW Version Indic...

Page 12: ...he controller will lose its positioning capability and you will have to de energize the unit for at least five seconds to remedy the situation If you want to test or force the commissioning damper use the jumper connections shown below or use the AST 10 hand held micro terminal Checking the min flow If possible zero volt is transmitted from the room unit or the main control system If this possibil...

Page 13: ...n nect it to the same terminal that the motor conductors are connected to See the wiring diagram for the AST 10 supplied in the instrument case 1 Press on Vmax change to the required value with the buttons press SET to confirm the change 2 Press on Vmin change to the required value with the buttons press SET to confirm the change 3 With Y you can read the control voltage set point transmitted from...

Page 14: ...1 2 6 3 9 125 124 472 245 61 77 180 401 2 9 4 0 160 159 472 285 61 60 215 401 3 3 4 8 200 199 472 335 61 40 255 401 4 0 5 8 250 249 522 395 61 15 305 452 4 9 7 8 315 314 552 465 61 370 452 6 5 9 7 400 399 684 553 61 462 614 10 7 14 9 500 499 810 653 61 565 740 15 7 21 3 250 Figure 34 VART 5 rectangular Figure 33 VAR 4 circular Figure 32 VAR 1 IR rectangular insulated casing Figure 31 VART 5 circul...

Reviews: