background image

BLB

d

Installation – Commissioning – Maintenance

20140912

Maintenance

The mixing box is equipped with an inspection cover 
made of plexiglas. The motor is coupled to the mixing 
box damper blade via connecting rods and a spindle 
that extends into the mixing box through a brass bush. 
The inspection cover can be dismantled, as required. It is 
advisable to switch off the ventilation before you disman-
tle the inspection cover.
Check the linkage system between the motor and the 
damper blade. Make sure that all the parts are in place 
and that screws have not come loose.
The spindle and the brass bush should be checked at 
regular intervals. Make sure that the spindle runs easily 
through the brass bush. Whenever the need arises the 
spindle should be cleaned with appropriate degreasing 
agent; then it should be oiled with a thin oil film and 
wiped dry of any excess oil.
The respective service function staff must determine the 
time interval for inspection. This depends on how clean 
the supply air is and how the ambient environment looks.
We recommend inspection at least once a year.  
We recommend lubricating the spindle with a foodstuff-
classified penetrating maintenance oil, such as Omega 
638 food grade 4.

REACT

RTC

BLB

Figure 1. Description of the function of the BLB for an electric 
control system in combination with the REACT and RTC.

4

3

1

2

Figure 2.
1. Brass bush
2. Spindle
3. Connecting rods
4. Plexiglas

Reviews:

Related manuals for BLBd