74
We reserve the right to make changes without any prior notice.
Translation from original instructions
SYMPTOM
LIKELY CAUSE
POSSIBLE SOLUTION
Presence of oil on the discharge of the
safety valve.
Opening of the valve due to failure of
the protective devices to operate.
Check that the high pressure switches
are working and, if necessary, replace
them.
The valve must be replaced.
Opening of the valve due to overtem-
perature.
Replace the valve and restore the
charge.
Water leaks from the pump on first
start-up
Bedding in the mechanical seal
Pressurize the pump body 2 or 3 times
by closing and opening the delivery
valve so as to correctly bed in the seal.