Service
[ S ] 51
Error Messages
Filter Run Time
Indicates that it has been more than 8.700 operational hours (or
roughly one year) since the last filter change.
Note
After filter has been replaced select Service Operation to reset
the hour counter.
Filter Contamination
One or both fans indicate an error because the air flow is
restricted due to a dirty filter (this is not displayed until after 3
days).
This error message can also be triggered by other air flow
obstructions such as (under dimensioned opening between
supply and extract air or DIP-switch setting for extract air is set
too high).
WiFi
The red LED will appear continuously if the WiFi of the freeAir
has been activated using the freeAir Connect USB but is not
connected to the local WiFi router.
This may be due to the wrong WiFi name or password, too far
from the router or a problem with the router or the internet.
The WiFi option is available up from pcb version 9.