9.3.2 Outdoor Temperature Compensation
Airflow
Outdoor temperature compensation of the airflow can be
activated if it is desired to reduce the airflow in the winter-
time.
In the flow regulation mode, the current airflow is re-
duced.
The function has no effect if the airflow is demand-con-
trolled.
The airflow is reduced as a percentage of the current
airflow/pressure.
Settings:
Value
Setting
Factory
range setting
Y1, max permissible reduction 0-50%
30 %
X1, breakpoint
-30 – -10 °C
-20 °C
X2, breakpoint
-10 – +15 °C
+10 °C
Outdoor air compensation according to factory settings
involves:
Outdoor tempe10 °C (Breakpoint X2): Compen-
sation starts and gradually proceeds between 0–30 %
down to outdoor air temperature -20 °C.
Outdoor air temperature -20 °C (Breakpoint X1): Con-
stant compensation proceeds at 30 % (max reduction
Y1).
0%
-50%
-40%
-30%
-20%
-30
-20
-10
0
+10
+20
-10%
Y = Airflow reduction %
X = Outdoor air temperature °C
X1
X2
Y1