GB.COOLDXS.INS.100507
8 www.swegon.com
We reserve the right to alter specifi cations.
min. 1500 mm
min. 1500 mm
GOLD RX/PX/CX,
supply air duct in lower level
3.3 Basic installation principle
The cooling unit is connected to the supply air duct of the
air handling unit, see drawing. The airfl ow through the
bottom section of the cooling unit should be as indicted
by the arrow affi xed on the side of the cooling unit.
The dimensions and capacity of the cooling unit is
matched for connection to the GOLD air handling unit in
sizes 12 - 80.
For a list of the capacity sizes of cooling units matched
to respective unit size,
see Section 10 General technical
data.
3.2 Arrangement
The cooling unit should be placed outdoors (extra accesso-
ries are not necessary). The GOLD unit can also be placed
outdoors with accessories for outdoor installation. It is also
possible to install the GOLD unit indoors and simply route
the supply air duct out to the cooling unit.
The required free distance for servicing by the inspection
side and back side of the cooling unit is 1000 mm. Re-
quired free distance for airfl ow through condenser coils in
the upper level of the cooling unit is 1500 mm. The space
above the cooling unit should be completely free. See
illustration.
Illustrations on this page show the right-hand version; the
cooling unit is also in the left-hand version.
1500 mm
1000 mm
1000 mm
1500 mm
Completely free space.
GOLD RX/CX,
supply air duct in upper level
GOLD SD,
supply air unit
Supply air
Inspection side
Rear