Installation

The air diffuser is normally suspended from the ceiling. An M8 pop 
nut, i.e. a threaded grommet that facilitates installation, is in the 
centre of the top of the air diffuser. On the size 315 and 400 air 
diffusers, there are two M8 pop nuts for more stable mounting, 
see figure 2 and 3. 

Commissioning

Commissioning should be carried out with the diffuser face 
mounted. Pull the measuring tubes and the damper adjustment 
cords out of the air diffuser through one disc in the diffuser face. 
Then connect the manometer to the correct measuring tube(s): 
two blue tubes for supply air and one transparent tube for extract 
air. The rated coefficient of performance of the air register can 
be used in a calculation to determine the required commissioning 
pressure. Conclude commissioning by adjusting the damper to the 
correct blade position, tie a commissioning knot in the damper 
cords to indicate the damper position. See Figure 2.
The K-factor is specified on the product’s identification label and 
last in these instructions.

Maintenance

• 

Clean the air diffuser if needed with lukewarm water and 

dishwashing detergent added.

• 

The duct system can be accessed and lightly pulling the 

spring-loaded diffuser front downwards and then tilting, see 

figure 1.

• 

Dismantle the perforated air distribution plate located on the 

inlet as shown in figure 4.

• 

Loosen the damper in the inlet from its bayonet fastening by 
rotating to the side.

Length of straight duct

Type of obstruction upstream of

Length of straight duct 

upstream of the EAGLE Free

EAGLE Free

m

2

 = 5%

m

2

 = 10%

One 90° bend

3 ·Ød

2 ·Ød

Two 90°bends in the same plane

4 ·Ød

2 ·Ød

Two 90° bends in alignment at 
right angles to one another.

4 ·Ød

2 ·Ød

One 45° damper

6 ·Ød

3 ·Ød

One T-piece

4 ·Ød

3 ·Ød

m

2

 = accuracy of the method according to NVG’s report T32:1982

Figure 2. Installation. Commissioning. Maintenance.

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

k

p

q

=

k

p

q

=

(    )

2

EAGLE Free x 

Tomelilla

Sweden

XXX

k = XX

k

p

q

TILLUFT / SUPPLY AIR

TILLUFT / SUPPLY AIR

FRÅ

NLU

FT /

 EXTR

ACT AI

R

Figur 1. Spring-loaded diffuser front. 

Figure 4. 

Dismantling of the perforated air distribution plate. 

Figure 3a. Alternative installation. 

Applies only for
size 315 & 400

Figure 3b.Extra M8 pop nut, size 315 and 400. 

EAGLE 

Free f

Installation – Commissioning – Maintenance