Installation

The air diffuser is normally suspended from the ceiling. 
An M8 pop nut, i.e. a threaded grommet that facilitates 
installation, is in the centre of the top of the air diffuser. 
On the size 315 and 400 air diffusers, there are two M8 
pop nuts for more stable mounting, see figure 1 and 3. 

Commissioning

Commissioning should be carried out with the diffuser 
face mounted. Pull the measuring tubes and the damper 
adjustment cords out of the air diffuser through one 
nozzle in the diffuser face. Then connect the manome-
ter to the correct measuring tube(s): two blue tubes for 
supply air and one transparent tube for extract air. The 
rated coefficient of performance of the air register can be 
used in a calculation to determine the required commissi-
oning pressure. Conclude commissioning by adjusting the 
damper to the correct blade position, tie a commissioning 
knot in the damper cords to indicate the damper position. 
See Figure 1.
The K-factor is specified on the product’s identification 
label and last in these instructions.

Maintenance

•  Clean the air diffuser if needed with lukewarm water 

and dishwashing detergent added.

•  The duct system can be accessed and lightly pulling 

the spring-loaded diffuser front downwards and then 
tilting, see figure 2.

•  Dismantle the perforated air distribution plate located 

on the inlet as shown in figure 4.

•  Loosen the damper in the inlet from its bayonet fastening 

by rotating to the side.

Length of straight duct

Type of obstruction upstream of
EAGLE Free

Length of straight duct 

upstream of the EAGLE 

Free

m

2

 = 5%

m

2

 = 10%

One 90° bend

3 ·Ød

2 ·Ød

Two 90°bends in the same plane

4 ·Ød

2 ·Ød

Two 90° bends in alignment at 
right angles to one another.

4 ·Ød

2 ·Ød

One 45° damper

6 ·Ød

3 ·Ød

One T-piece

4 ·Ød

3 ·Ød

m

2

 = accuracy of the method according to NVG’s report T32:1982

Figure 1. Installation. Commissioning. Maintenance.

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

k

p

q

=

k

p

q

=

(    )

2

EAGLE Free x 

Tomelilla

Sweden

XXX

k = XX

k

p

q

TILLUFT / SUPPLY AIR

TILLUFT / SUPPLY AIR

FRÅ

NLU

FT /

 EXTR

ACT AI

R

Figure 2. Spring-loaded diffuser front.

EAGLE

 Free g

Installation – Commissioning – Maintenance

20201008