background image

EAGLE

 Wall b

Installation – Commissioning – Maintenance

20210525

Installation

See Figure 1.
1.  Cut the opening in the wall. The size of the opening 

should be according to dimensions I x J, which are 
given in the Dimensions table on page 2. 

2.  Place the commissioning box in the opening.
3.  Insert the mounting frame into the commissioning 

box and secure it with screws in the short sides to the 
commissioning box and to the wall structure.

4.  The assembly and dismantling of the component 

parts are shown in Figure 1.

5.  Press the diffuser face to engage it in the mounting 

frame.

Commissioning

Commissioning must be carried out with the diffuser 
face mounted. Pull the measuring tube and the damper 
adjustment cords out of the air diffuser through a disc. 
Connect a manometer to the measuring tube. The desired 
commissioning pressure can be calculated using the rated 
coefficient of performance of the air diffuser. Set the 
damper to the correct blade position, tie a commissioning 
knot in the damper cords to indicate the damper position, 
then lock the cords.

Maintenance

The air diffuser can be cleaned, if necessary, using luke-
warm water with dishwashing detergent added or by 
vacuum cleaning using a brush nozzle. The duct system 
can be accessed after the air diffuser section has been 
removed, the acoustic baffle has been withdrawn, the air 
distribution discs have been moved to the side and the 
damper has been turned and withdrawn from its fastener 
from the inlet. See Figure 1.

Environment

The Building Materials Declaration is available from www.
swegon.com.

To secure baffle (4) in bayonet catch and to secure the octagonal 
perforated face plate (3) against the duct connection.
1. Commissioning box
2. Damper action, bayonet catch
3. Octagonal air distribution plate
4. Air distribution plate
5. Mounting frame + air diffuser

Figure 1. Installation. Commissioning.

p

k-faktor

EAGLE Wall

Tomelilla

Sweden

400-200

+ALVT1 400-200-160-B
k-faktor=14,6/27,8

k

k

p

q

=

k

p

q

=

(    )

2

= uppmätt flöde l/s  

p

 = aktuellt mättryck (Pa)

k

 = injusteringsfaktor

5

q

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

0xD / ±5%

0xD / ±5%

2xD / ±10%

Figure 2. Installation alternatives, applies for all connections (B, K)

Reviews: