Installation

The air diffuser is normally suspended from the ceiling. 
An M8 pop nut, i.e. a threaded grommet that facilitates 
installation, is provided at the top and in the centre of the 
air diffuser. On sizes 315 and 400, there are two M8 pop 
nuts for more stable mounting, see figure 1 and 3.
Alternative installation in pre-punched Ø10 mm hole, see 
figure 3b.

Commissioning

Commissioning should be carried out with the wall dif-
fuser face mounted. Pull the measuring tubes and damper 
adjustment cords out of the air diffuser through the hole 
in the front. Then connect the manometer to the cor-
rect measuring tube(s); A transparent measuring tube for 
extract air. The rated coefficient of performance of the 
air diffuser can be used in a calculation to determine the 
required commissioning pressure. Conclude commissio-
ning by adjusting the damper to the correct blade posi-
tion, tie a commissioning knot in the damper cords to 
indicate the damper position. See Figure 1.
The K-factor is specified on the product’s identification 
label and last in these instructions.

Maintenance

•  Clean the air diffuser if needed with lukewarm water 

and dishwashing detergent added.

•  The duct system can be accessed by lightly pulling 

the spring-loaded diffuser face downwards and then 
tilting, see figure 4.

•  Dismantle the perforated air distribution plate located 

on the inlet as shown in figure 5.

•  Loosen the damper in the inlet from its bayonet fastening 

by rotating to the side.

Figure 1. Installation. Commissioning. Maintenance.

q

 = measured flow l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

0xD / ±5%

0xD / ±5%

2xD / ±10%

Figure 2. Length of straight section of duct

EXP

 Free b

Installation – Commissioning – Maintenance

20220217

Summary of Contents for EXP Free b

Page 1: ...r can be used in a calculation to determine the required commissioning pressure Conclude commissio ning by adjusting the damper to the correct blade posi tion tie a commissioning knot in the damper cords to indicate the damper position See Figure 1 The K factor is specified on the product s identification label and last in these instructions Maintenance Clean the air diffuser if needed with lukewa...

Page 2: ...ont Applies only for size 315 400 We recommend wearing gloves as there is a risk of cut injuries to the hands fingers Figure 3b Alternative installation in pre punched Ø10 mm hole M8 threaded rod for oscillation Installed directly on the ceiling EXP Free 2 Swegon reserves the right to alter specifications 20220217 ...

Page 3: ...s in the sleeve plate The damper is turned anticlockwise and pulled out The number holes in the damper must correspond with the number of holes in the sleeve plate We recommend wearing gloves as there is a risk of cut injuries to the hands fingers 3 20220217 Swegon reserves the right to alter specifications EXP Free ...

Page 4: ... NOTE The blue tubes can be used if the product is converted for supply air with the distributor being replaced with nozzles for COLIBRI Fb and EAGLE Fg Dimensions and weight Size A B C D E Weight kg 100 304 192 118 99 96 2 8 125 380 217 210 124 108 3 7 160 456 252 220 159 126 5 0 200 568 288 230 199 144 7 5 250 568 338 275 249 169 8 5 315 700 388 330 314 194 12 4 400 700 488 350 399 244 15 4 EXP ...

Reviews: