GB.GOLDLP.170830
24 www.swegon.com
We reserve the right to alter specifications without notice.
9.2.7 External Temperature Sensors
The IQnomic control unit has provision for wiring an
external room sensor and/or external outdoor sensor. The
sensor can be used when the internal sensor of the unit
does not provide representative values.
External Extract air/Room can measure the extract air
temperature in a larger room instead of the temperature
inside the air handling unit.
External Outdoor measures the outdoor air temperature
outdoors, instead of the temperature inside the air han-
dling unit.
Connect the TBLZ-1-24-2 sensor by means of the modular
cable supplied, to an optional connection marked Internal
BUS 1.
Sensor TBLZ-1-24-2 can be used both as a room sensor
and an outdoor sensor. They must therefore be addressed
according to function using the function selector switch
on the sensor. The function selector switch must be in
Position 1 if the sensor is used as a room sensor and in
Position 2 if it is used as an outdoor sensor.
If the TBLZ-1-24-2 sensor is installed outdoors, it must be
mounted inside an air-tight enclosure.
As an alternative, a temperature reading can be commu-
nicated to the air handling via communication from e.g. a
main system.
The alarm setting indicates how long the alarm will be
delayed if communication is lost.
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
AIR FLOW/PRESSURE
FILTER
OPERATION
HEATING
HUMIDITY
COOLING
IN/OUTPUTS
IQnomic Plus
ALL YEAR COMFORT
OPTIMIZE
* TEMPERATURE *
TEMPERATURE REG
OUTDOOR TEMP COMP
SUMMER NIGHT COOL
INTERM. NIGHT HEAT
MORNING BOOST
SETPOINT TEMP DISPL
EXT. SENSORS