Function
Factory preset value
Adjusted value
All Year Comfort
X Inact.
Cool.
Heat.
C+H
Inact.
Cool.
Heat.
C+H
Heating water temp. (°C)
30
Cooling water temp. (°C)
14
Outdoor comp., Heating water
X Inact.
Active
Inact.
Active
Outdoor temp. (X1) (°C)
-20
Heating water (Y1)(°C)
40
Outdoor temp. (X2)(°C)
5
Heating water (Y2)(°C)
30
Outdoor temp. (X3)(°C)
15
Heating water (Y3)(°C)
20
Outdoor comp., Cooling water
X Inact.
Active
Inact.
Active
Outdoor temp. (X1) (°C)
10
Cooling water (Y1)(°C)
22
Outdoor temp. (X2)(°C)
20
Cooling water (Y2)(°C)
18
Outdoor temp. (X3)(°C)
25
Cooling water (Y3)(°C)
14
Room comp., Heating water
X Inact.
Active
Inact.
Active
Room temperature (°C)
21
P-band (°C)
5
Night blocking
Inact.
Active
Inact.
Active
Room comp., Cooling water
X Inact.
Active
Inact.
Active
Room temperature (°C)
21
P-band (°C)
5
Night blocking
Inact.
Active
Inact.
Active
Night comp., Heating water
X Inact.
Active
Inact.
Active
Temp. comp. (°C)
-2
Night comp., Cooling water
X Inact.
Active
Inact.
Active
Temp. comp. (°C)
2
Night comp.
X Inact.
Active
Inact.
Active
Channel 1, Start, Stop, Weekday
Inactive
Channel 2, Start, Stop, Weekday
Inactive
Pump operation, Heating water
Outdoor temp. Start (°C)
15
Outdoor temp. Stop (°C)
18
Pump operation, Cooling water
Outdoor temp. Start (°C)
-20
Outdoor temp. Stop (°C)
-25
Alarm function, Heating water
Pump alarm
X Inact.
Open
Close
Cont.
Inact.
Open
Close
Cont.
Valve
X Inact.
Active
Inact.
Active
Alarm function, Cooling water
Pump alarm
X Inact.
Open
Close
Cont.
Inact.
Open
Close
Cont.
Valve
X Inact.
Active
Inact.
Active
Exercising, Heating water
X Inact.
Pump
P+V
Valve
Inact.
Pump
P+V
Valve
Exercising period, (min)
3
Interval (h)
24
Exercising, Cooling water
X Inact.
Pump
P+V
Valvev
Inact.
Pump
P+V
Valve
Exercising period, (min)
3
Interval (h)
24
Dew point comp.
X Inact.
Active
Inact.
Active
Neutral zone (°C)
2
Comp. air flow (%)
10