GB.GOLDLP.170830
68 www.swegon.com
We reserve the right to alter specifications without notice.
Alarm No.:
Function
Factory preset value
Adjusted value
Priority
Indication
Effect
Priority
Indication
Effect
0=blocked
LED
0=Operat. 0=blockedt
LED
0=Operat.
A=A alarm
0=Off
1=Stop
A=A alarm
0=Off
1=Stop
B=B alarm
1=On
B=B alarm
1=On
43
Ext. alarm No.2 tripped
B ***
1
0
44
SA duct pressure below setpoint
B ***
1
0
45
EA duct pressure below setpoint
B ***
1
0
46
SA duct pressure above setpoint
B ***
1
0
47
EA duct pressure above setpoint
B ***
1
0
48
Supply airflow below setpoint
B ***
1
0
49
Extract airflow below setpoint
B ***
1
0
50
Supply airflow above setpoint
B ***
1
0
51
Extract airflow above setpoint
B ***
1
0
52
Supply air filter dirty
B ***
1
0
53
Extract air filter dirty
B ***
1
0
54
Service period past alarm limit
B ***
1
0
55
No comm. SA air flow pressure sensor
A ***
1
1
56
No comm. EA air flow pressure sensor
A ***
1
1
57
No comm. SA filter pressure sensor
B ***
1
0
58
No comm. EA filter pressure sensor
B ***
1
0
59
No comm. SA duct pressure sensor
A ***
1
1
60
No comm. EA duct pressure sensor
A ***
1
1
61
No comm. r.hx. pressure sensor
B ***
1
0
62
No communication to I/O-module No:0
B ***
1
0
63
No communication to I/O-module No:1
B ***
1
0
64
No communication to I/O-module No:2
B ***
1
0
65
No communication to I/O-module No:3
B ***
1
0
66
No communication to I/O-module No:4
B ***
1
0
67
No communication to I/O-module No:5
B ***
1
0
68
No communication to I/O-module No:6
B ***
1
0
69
No communication to I/O-module No:7
B ***
1
0
70
No communication to I/O-module No:8
B ***
1
0
71
No communication to I/O-module No:9
B ***
1
0
72
No communication to main controller I/O
A
1
1
75
Supply air humidity sensor faulty
A ***
1
1
76
Extract air humidity sensor faulty
A ***
1
1
83
Supply air, prefilter fouled.
B***
1
0
84
Exhaust air prefilter, fouled
B***
1
0
85
Cooling Output 1 tripped
A
1
0
86
Cooling Output 2 tripped
A
1
0
89
No comm. with press. sensor by SA prefilter
B***
1
0