background image

KITE 

Ceiling

Square ceiling diffuser for supply air

AIR FLOW - SOUND PRESSURE ROOM (Lp10A) *)

KITE CR
Size

25 dB(A)

30 dB(A)

35 dB(A)

l/s

m

3

/h

l/s

m

3

/h

l/s

m

3

/h

125-600

53

191

63

227

73

263

160-600

66

238

76

274

87

313

200-600

88

317

102

367

119

428

250-600

114

410

132

475

153

551

315-600

125

450

147

529

174

626

KITE CR
Size

ALS

Size

25 dB(A)

30 dB(A)

35 dB(A)

l/s

m

3

/h

l/s

m

3

/h

l/s

m

3

/h

125-600

100-125

33

119

39

140

47

169

160-600

125-160

47

169

56

202

67

241

200-600

160-200

75

270

87

313

102

367

250-600

200-250

101

364

118

425

137

493

315-600

250-315

129

464

149

536

172

619

The table shows supply air data for fully open damper.

*) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m

2

 

    room’s absorption area.

QUICK FACTS

 

Square slot diffuser designed for suspended ceiling 
system 600x600

 

Flush design

 

Supply air diffuser also works for extract air

 

Easy Access gives fast and easy installation and com-
missioning

 

Commissioning box ALS with one- or two-dimensional 
changes between duct and air diffuser connection

 

Available in a version with low installation height

 

Standard colour White RAL 9003

 

-

5 alternative standard colours

 

-

Other colours upon request

Summary of Contents for KITE Ceiling

Page 1: ...3 102 367 250 600 200 250 101 364 118 425 137 493 315 600 250 315 129 464 149 536 172 619 The table shows supply air data for fully open damper Lp10A Sound pressure incl A filter with 4 dB room attenuation and 10 m2 room s absorption area QUICK FACTS Square slot diffuser designed for suspended ceiling system 600x600 Flush design Supply air diffuser also works for extract air Easy Access gives fast...

Page 2: ...ment 3 Sizing 5 Sound data Air diffuser only 5 Sound data Air diffuser with the commissioning box 6 KITE CR and KITE CR with ALS 7 KITE CR Air diffuser only 7 KITE CR with ALS Supply air 8 KITE CR with ALS Extract air 10 Dimensions and weights 12 Specification 13 Specification text 13 KITE Ceiling 2 Swegon reserves the right to alter specifications 25 08 2020 ...

Page 3: ...ans of self tapping screws or blind rivets For flush mounting in fixed ceilings secure the air diffuser to the building structure through the top of the backing box The air diffuser and commissioning box with low installation height are centred with each other using the supplied locking strip Secure the diffuser in the correct position with screws or pop rivets in the underside of the commissionin...

Page 4: ...and commissioning box with low installation height Figure 4 Damper removal 0xD 5 0xD 5 2xD 10 Locate the eyelid and carefully press in the legs towards the air diffuser The face plate hangs on the corresponding side by the hinge KITE Ceiling 4 Swegon reserves the right to alter specifications 25 08 2020 ...

Page 5: ...315 600 10 13 10 2 7 15 25 28 Tol 2 2 2 2 2 2 2 2 Attenuation DL dB Table DL Size Mid frequency Octave band Hz 63 125 250 500 1000 2000 4000 8000 125 600 20 15 10 5 3 5 5 4 160 600 19 14 9 4 3 5 5 4 200 600 19 14 8 3 3 4 5 5 250 600 16 11 5 4 3 3 4 4 315 600 14 9 4 2 2 2 3 3 Tol 2 2 2 2 2 2 2 2 KITE CR Extract air Sound power level Lw dB Table KOK Size Mid frequency octave band Hz 63 125 250 500 1...

Page 6: ...0 19 16 13 16 16 Tol 2 2 2 2 2 2 2 2 Sound data Air diffuser with commissioning box KITE CR ALS Extract air One step Sound power level Lw dB Table KOK Size Mid frequency octave band Hz 63 125 250 500 1000 2000 4000 8000 125 600 4 9 6 2 4 9 14 23 160 600 1 11 7 1 4 8 14 22 200 600 5 11 5 1 4 8 14 24 250 600 1 10 1 3 2 6 13 23 315 600 4 11 4 2 2 5 11 21 Tol 2 2 2 2 2 2 2 2 KITE CR ALS Extract air Tw...

Page 7: ...Supply air The throw length l0 2 is measured under isothermal discharge conditions The recommended max permissible temperature below room temperature is 10 K To calculate the air stream diffusion air velocities in the occupied zone or sound levels in rooms with other dimen sions please refer to our calculation software available on www swegon com Δ Min flow required for obtaining sufficient commis...

Page 8: ...10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 160 600 ALS 100 160 Two steps pt Pa 40 50 100 200 m3 h 10 20 30 40 50 l s 100 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 160 600 ALS 125 160 One step pt Pa 100 200 300 400 m3 h 20 30 40 50 100 l s 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m...

Page 9: ...15 One step pt Pa 200 300 400 500 1000 m3 h 40 50 100 200 300 l s 400 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 2 3 4 5 10 m 0 2 l KITE CR 200 600 ALS 125 200 Two steps pt Pa 100 200 300 400 m3 h 20 30 40 50 100 l s 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 250 600 ALS 160 250 Two steps pt Pa 100 200 300 400 500 m3 h 20 30 40 50 100 l...

Page 10: ... 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 160 600 ALS 125 160 One step KITE CR 200 600 ALS 125 200 Two steps Relationship connection dimensions A duct connection B air diffuser connection Explanation of step model One step A dimensional change between A and B e g A Ø160 mm and B Ø200 mm Two steps Two dimensional changes between A and B e g A Ø160 mm and B Ø250 mm KITE CR 125 600 ALS 1...

Page 11: ...0 ALS 200 250 One step pt Pa 100 200 300 400 500 m3 h 20 30 40 50 100 l s 200 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 315 600 ALS 200 315 Two steps pt Pa 100 200 300 400 500 m3 h 30 40 50 100 200 l s 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 315 600 ALS 250 315 One step pt Pa 200 300 400 500 m3 h 30 40 50 100 200 l s 300 5 10 20 30 40 50 100 200 20 25 30 35 40 d...

Page 12: ...65 115 8 2 315 600 595 622 388 249 315 385 342 83 40 220 177 575 140 10 9 KITE CR with ALS Two steps Size A B C ØD Ød E1 E2 F1 F2 G1 G2 H K Weight kg 160 600 595 342 252 99 160 225 182 83 40 145 102 315 80 5 5 200 600 595 404 288 124 200 249 206 83 40 158 115 355 80 6 2 250 600 595 504 332 159 250 284 241 83 40 175 132 450 100 7 4 315 600 595 622 388 199 315 324 281 83 40 195 152 550 115 9 7 CL Ce...

Page 13: ...only if a low version is required Frame SAR b K aaa Version K square For size 125 600 600 160 600 600 200 600 600 250 600 600 315 600 600 Specification text Swegon s complete square slot diffuser for ceiling installation type KITE ceiling air diffuser with ALS commissioning box and the following functions Designed for modular suspended ceilings Easy Access Removable commissioning damper Method of ...

Reviews: