Sizing
• Sound levels dB(A) are applicable to rooms with an
equivalent sound absorption area of 10 m
2
.
• The throw length l
0.2
is measured under isothermal
discharge conditions.
• The recommended max. permissible temperature
below room temperature is 10 K.
• To calculate the air stream diffusion, air velocities in
the occupied zone or sound levels in rooms with other
dimensions, please refer to our calculation software,
which is at www.swegon.com.
Sound data – Air diffuser only
KITE CR – Supply air
Sound power level L
w
(dB)
Table K
OK
Size
Mid-frequency (octave band) Hz
63 125 250 500 1000 2000 4000
8000
125-600
-2
6
4
1
1
-7
-18
-26
160-600
-3
9
5
-2
1
-7
-15
-27
200-600
3
12
8
0
-2
-11
-19
-25
250-600
8
12
8
1
-4
-10
-20
-26
315-600
10
13
10
2
-7
-15
-25
-28
Tol. ±
2
2
2
2
2
2
2
2
Attenuation
D
L (dB)
Table
D
L
Size
Mid-frequency (Octave band) Hz
63 125 250 500 1000 2000 4000
8000
125-600
20
15
10
5
3
5
5
4
160-600
19
14
9
4
3
5
5
4
200-600
19
14
8
3
3
4
5
5
250-600
16
11
5
4
3
3
4
4
315-600
14
9
4
2
2
2
3
3
Tol. ±
2
2
2
2
2
2
2
2
KITE CR – Extract air
Sound power level L
w
(dB)
Table K
OK
Size
Mid-frequency (octave band) Hz
63 125 250 500 1000 2000 4000
8000
125-600
-12
7
5
1
0
-6
-18
-28
160-600
-4
9
6
1
0
-12
-24
-28
200-600
-3
11
5
1
0
-13
-25
-29
250-600
0
13
5
0
-1
-9
-19
-28
315-600
0
12
5
-1
-1
-4
-12
-23
Tol. ±
2
2
2
2
2
2
2
2
Attenuation
D
L (dB)
Table
D
L
Size
Mid-frequency (Octave band) Hz
63 125 250 500 1000 2000 4000
8000
125-600
20
15
10
5
3
5
5
4
160-600
19
14
9
4
3
5
5
4
200-600
19
14
8
3
3
4
5
5
250-600
16
11
5
4
3
3
4
4
315-600
14
9
4
2
2
2
3
3
Tol. ±
2
2
2
2
2
2
2
2
5
25/08/2020 Swegon reserves the right to alter specifications.