Sizing

•  Sound levels dB(A) are applicable to rooms with an 

equivalent sound absorption area of 10 m

2

•  The throw length l

0.2

 is measured under isothermal 

discharge conditions.

•  The recommended max. permissible temperature 

below room temperature is 10 K.

•  To calculate the air stream diffusion, air velocities in 

the occupied zone or sound levels in rooms with other 
dimensions, please refer to our calculation software, 
which is at www.swegon.com.

Sound data – Air diffuser only

KITE CR – Supply air
Sound power level L

w

(dB) 

Table K

OK

Size

Mid-frequency (octave band) Hz

63 125 250 500 1000 2000 4000

8000

125-600

-2

6

4

1

1

-7

-18

-26

160-600

-3

9

5

-2

1

-7

-15

-27

200-600

3

12

8

0

-2

-11

-19

-25

250-600

8

12

8

1

-4

-10

-20

-26

315-600

10

13

10

2

-7

-15

-25

-28

Tol. ±

2

2

2

2

2

2

2

2

Attenuation 

D

L (dB) 

Table 

D

L

Size

Mid-frequency (Octave band) Hz

63 125 250 500 1000 2000 4000

8000

125-600

20

15

10

5

3

5

5

4

160-600

19

14

9

4

3

5

5

4

200-600

19

14

8

3

3

4

5

5

250-600

16

11

5

4

3

3

4

4

315-600

14

9

4

2

2

2

3

3

Tol. ±

2

2

2

2

2

2

2

2

KITE CR – Extract air

Sound power level L

w

(dB) 

Table K

OK

Size

Mid-frequency (octave band) Hz

63 125 250 500 1000 2000 4000

8000

125-600

-12

7

5

1

0

-6

-18

-28

160-600

-4

9

6

1

0

-12

-24

-28

200-600

-3

11

5

1

0

-13

-25

-29

250-600

0

13

5

0

-1

-9

-19

-28

315-600

0

12

5

-1

-1

-4

-12

-23

Tol. ±

2

2

2

2

2

2

2

2

Attenuation 

D

L (dB) 

Table 

D

L

Size

Mid-frequency (Octave band) Hz

63 125 250 500 1000 2000 4000

8000

125-600

20

15

10

5

3

5

5

4

160-600

19

14

9

4

3

5

5

4

200-600

19

14

8

3

3

4

5

5

250-600

16

11

5

4

3

3

4

4

315-600

14

9

4

2

2

2

3

3

Tol. ±

2

2

2

2

2

2

2

2

5

25/08/2020                          Swegon reserves the right to alter specifications.

KITE 

Ceiling

Summary of Contents for KITE Ceiling

Page 1: ...3 102 367 250 600 200 250 101 364 118 425 137 493 315 600 250 315 129 464 149 536 172 619 The table shows supply air data for fully open damper Lp10A Sound pressure incl A filter with 4 dB room attenuation and 10 m2 room s absorption area QUICK FACTS Square slot diffuser designed for suspended ceiling system 600x600 Flush design Supply air diffuser also works for extract air Easy Access gives fast...

Page 2: ...ment 3 Sizing 5 Sound data Air diffuser only 5 Sound data Air diffuser with the commissioning box 6 KITE CR and KITE CR with ALS 7 KITE CR Air diffuser only 7 KITE CR with ALS Supply air 8 KITE CR with ALS Extract air 10 Dimensions and weights 12 Specification 13 Specification text 13 KITE Ceiling 2 Swegon reserves the right to alter specifications 25 08 2020 ...

Page 3: ...ans of self tapping screws or blind rivets For flush mounting in fixed ceilings secure the air diffuser to the building structure through the top of the backing box The air diffuser and commissioning box with low installation height are centred with each other using the supplied locking strip Secure the diffuser in the correct position with screws or pop rivets in the underside of the commissionin...

Page 4: ...and commissioning box with low installation height Figure 4 Damper removal 0xD 5 0xD 5 2xD 10 Locate the eyelid and carefully press in the legs towards the air diffuser The face plate hangs on the corresponding side by the hinge KITE Ceiling 4 Swegon reserves the right to alter specifications 25 08 2020 ...

Page 5: ...315 600 10 13 10 2 7 15 25 28 Tol 2 2 2 2 2 2 2 2 Attenuation DL dB Table DL Size Mid frequency Octave band Hz 63 125 250 500 1000 2000 4000 8000 125 600 20 15 10 5 3 5 5 4 160 600 19 14 9 4 3 5 5 4 200 600 19 14 8 3 3 4 5 5 250 600 16 11 5 4 3 3 4 4 315 600 14 9 4 2 2 2 3 3 Tol 2 2 2 2 2 2 2 2 KITE CR Extract air Sound power level Lw dB Table KOK Size Mid frequency octave band Hz 63 125 250 500 1...

Page 6: ...0 19 16 13 16 16 Tol 2 2 2 2 2 2 2 2 Sound data Air diffuser with commissioning box KITE CR ALS Extract air One step Sound power level Lw dB Table KOK Size Mid frequency octave band Hz 63 125 250 500 1000 2000 4000 8000 125 600 4 9 6 2 4 9 14 23 160 600 1 11 7 1 4 8 14 22 200 600 5 11 5 1 4 8 14 24 250 600 1 10 1 3 2 6 13 23 315 600 4 11 4 2 2 5 11 21 Tol 2 2 2 2 2 2 2 2 KITE CR ALS Extract air Tw...

Page 7: ...Supply air The throw length l0 2 is measured under isothermal discharge conditions The recommended max permissible temperature below room temperature is 10 K To calculate the air stream diffusion air velocities in the occupied zone or sound levels in rooms with other dimen sions please refer to our calculation software available on www swegon com Δ Min flow required for obtaining sufficient commis...

Page 8: ...10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 160 600 ALS 100 160 Two steps pt Pa 40 50 100 200 m3 h 10 20 30 40 50 l s 100 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 160 600 ALS 125 160 One step pt Pa 100 200 300 400 m3 h 20 30 40 50 100 l s 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m...

Page 9: ...15 One step pt Pa 200 300 400 500 1000 m3 h 40 50 100 200 300 l s 400 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 2 3 4 5 10 m 0 2 l KITE CR 200 600 ALS 125 200 Two steps pt Pa 100 200 300 400 m3 h 20 30 40 50 100 l s 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 0 100 1 2 3 4 5 m 0 2 l KITE CR 250 600 ALS 160 250 Two steps pt Pa 100 200 300 400 500 m3 h 20 30 40 50 100 l...

Page 10: ... 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 160 600 ALS 125 160 One step KITE CR 200 600 ALS 125 200 Two steps Relationship connection dimensions A duct connection B air diffuser connection Explanation of step model One step A dimensional change between A and B e g A Ø160 mm and B Ø200 mm Two steps Two dimensional changes between A and B e g A Ø160 mm and B Ø250 mm KITE CR 125 600 ALS 1...

Page 11: ...0 ALS 200 250 One step pt Pa 100 200 300 400 500 m3 h 20 30 40 50 100 l s 200 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 315 600 ALS 200 315 Two steps pt Pa 100 200 300 400 500 m3 h 30 40 50 100 200 l s 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 KITE CR 315 600 ALS 250 315 One step pt Pa 200 300 400 500 m3 h 30 40 50 100 200 l s 300 5 10 20 30 40 50 100 200 20 25 30 35 40 d...

Page 12: ...65 115 8 2 315 600 595 622 388 249 315 385 342 83 40 220 177 575 140 10 9 KITE CR with ALS Two steps Size A B C ØD Ød E1 E2 F1 F2 G1 G2 H K Weight kg 160 600 595 342 252 99 160 225 182 83 40 145 102 315 80 5 5 200 600 595 404 288 124 200 249 206 83 40 158 115 355 80 6 2 250 600 595 504 332 159 250 284 241 83 40 175 132 450 100 7 4 315 600 595 622 388 199 315 324 281 83 40 195 152 550 115 9 7 CL Ce...

Page 13: ...only if a low version is required Frame SAR b K aaa Version K square For size 125 600 600 160 600 600 200 600 600 250 600 600 315 600 600 Specification text Swegon s complete square slot diffuser for ceiling installation type KITE ceiling air diffuser with ALS commissioning box and the following functions Designed for modular suspended ceilings Easy Access Removable commissioning damper Method of ...

Reviews: