background image

9

06/11/2021                          Swegon reserves the right to alter specifications.

PARAGON 

d

Air connection

All variants have an air connection Ø125. 
The standard variant has the air connection centered on 
the back of the product for easy access from both ends 
and back. 
The suite variant, which is only available in length 1400 
mm, has two parallel air connections on the back (2x 
Ø125). 

Connection dimensions air

Variant

Length

Air connetion

(mm)

1 x Ø 125

2 x Ø 125

1: Standard

800, 1100, 1400

Yes

No

2: Suite

1400

No

Yes

PARAGON standard, view from the back (L)

PARAGON suite, view from the back (R)

PARAGON suite, view from the back (L)

PARAGON standard, view from the back (R)

Summary of Contents for PARAGON d

Page 1: ... 2 Service maintenance 2 Product warranty 2 Dimensions and weight 3 Installation 4 Cutout dimensions 4 Suspension 5 Water connection 7 Connecting water 7 Water connection CCO valve 8 Air connection 9 Connection dimensions air 9 Air connections 10 Mounting grills 11 Control equipment 12 Terminal block 12 PARAGON 12 LUNA 12 URC1 VAV 13 Commissioning 14 K factor setting 14 Maintenance 15 Symbols Warn...

Page 2: ... Install the product for easy access during service maintenance Avoid installing the product near a heat source Check to make sure that the product does not have any visible defects Check that the product is properly secured after it has been installed Secure cables with cable ties Check that all cables are properly secured in place after installation Disposal Waste must be handled according to lo...

Page 3: ...1 39 800 L X 125 14 0 16 9 1 38 PARAGON d 1100 Length Type Dim Dry weightt kg Water volume l mm Ø without grills incl grills cooling heating 1100 R A 125 18 8 22 6 1 93 1100 L A 125 18 8 22 6 1 92 1100 R B 125 18 8 22 6 1 93 0 52 1100 L B 125 18 8 22 6 1 92 0 51 1100 R X 125 18 8 22 6 1 93 1100 L X 125 18 8 22 6 1 92 PARAGON d 1400 Length Type Dim Dry weight kg Water volume l mm Ø without grills I...

Page 4: ... specifications 06 11 2021 Cutout dimensions Installation 23 5 315 92 5 92 5 25 6 23 5 315 92 5 92 5 25 6 805 1105 1405 10 785 1085 1385 10 40 70 390 10 193 250 140 10 121 4 91 205 569 0 20 153 153 0 378 405 91 569 0 20 153 153 121 4 205 0 378 405 ...

Page 5: ...021 Swegon reserves the right to alter specifications PARAGON d Suspension 23 5 8 5 11 7 6 222 5 146 6 15 Ø125 L A B 800 778 2 222 5 1100 1078 2 222 5 1400 1378 2 222 5 c c B c c A 823 1123 1423 722 250 250 250 ...

Page 6: ...PARAGON d 6 Swegon reserves the right to alter specifications 06 11 2021 M8 4 x ...

Page 7: ...n Return 800 1100 1400 DN15 external thread DN15 external thread Standard variant without factory fitted valves Length Cooling Heating mm Supply and return Supply and return 800 1100 1400 Plain pipe Plain pipe Cu Ø 12 x 1 0 mm Cu Ø 12 x 1 0 mm 23 5 315 92 5 92 5 25 6 Connecting water Connect the water pipes using push on couplings or compression ring couplings when the product is ordered without v...

Page 8: ...supply A2 Cooling water return B1 Heating water supply B2 Heating water return Water connection on back side B D B1 B2 505050 A1 A2 C Water connection CCO valve A1 Cooling water supply A2 Cooling water return B1 Heating water supply B2 Heating water return C CCO valve D Flexible hose Water connection CCO valve A1 A2 B1 B2 ...

Page 9: ...access from both ends and back The suite variant which is only available in length 1400 mm has two parallel air connections on the back 2x Ø125 Connection dimensions air Variant Length Air connetion mm 1 x Ø 125 2 x Ø 125 1 Standard 800 1100 1400 Yes No 2 Suite 1400 No Yes PARAGON standard view from the back L PARAGON suite view from the back R PARAGON suite view from the back L PARAGON standard v...

Page 10: ...PARAGON d 10 Swegon reserves the right to alter specifications 06 11 2021 Air connections Supply air kit Extract air kit A Min 770mm B Min 360mm A Min 70mm B Min 330mm ...

Page 11: ...11 06 11 2021 Swegon reserves the right to alter specifications PARAGON d Mounting grills Click Click ...

Page 12: ...4V G0 0 10V DC G0 G SENSOR CONDENS 0 10V DC CCO WCD2 24V G0 24V AC 24V G0 0 10V DC G0 G SENSOR CONDENS 0 10V DC CCO 942193004 24V G0 black white 24 24V AC POWER Aa 60 VA POWER Aa 20 VA WCD2 ACTUATORc 24V NC ACTUATORc 24V NC External connections Internal connections CG IV Y20 G0 Y10 Y1 24V AC DC Y2 G0 0 10 V DC G 24V AC DC G0 0V 0 10 V DC Temp sensor Cond sensor Modbus Modbus ...

Page 13: ... 2 2 2 3 2 4 2 5 black black white brown white y 24V brown blue blackY control signal styrsignal 0 10V DC RoHS Temperature sensor Window contact Valve actuator cooling Valve actuator heating Key card Condensation sensor CO2 sensor 24 V AC DC Cable USB RJ12 Cable adapter Pressure sensor Modbus Adapter 3xRJ12 Adapter 3xRJ12 Motor Sensor module VOC sensor A Max 48 VA Max 48 VA Max 48 VA The outputs o...

Page 14: ...factor i q k p l s i p k q C A B Example To achieve the required flow of 25 l s at 100 Pa requires k factor 2 5 A Find the product s length from left hand side of the k factor table B Read the required k factor on the row in question C Follow the vertical row and read the number of degrees at the bottom D Loosen the screw located in the knob s groove the knob then moves to the fully open position ...

Page 15: ...15 06 11 2021 Swegon reserves the right to alter specifications PARAGON d Maintenance ...

Page 16: ...PARAGON d 16 Swegon reserves the right to alter specifications 06 11 2021 Click Click ...

Reviews: