background image

1

Installation – Commissioning – Maintenance

20130806

PELICAN

TM

 

Ceiling Extract a

Accessories

Commissioning box:

ALS. The commissioning box is made of galvanized sheet 
steel and contains a removable commissioning damper, 
fixed measurement tapping and sound absorbing mate-
rial*

)

 with reinforced surface layer.

*

)

Fire resistance rated to B-s1,d0 in accordance with 

EN ISO 11925-2

Frame:

SAR K, for aesthetic installation of a lowered diffuser section.

Adapter:

ADAPTER, for adaptation to various variants and makes of 
systemized false ceilings: Ecophon, Gyproc, Dampa, etc. 
Used also for adaptation to alternative sizes of systemized 
false ceilings, e.g. 625 x 625 or 675 x 675.

Installation

To unfasten the diffuser face, press in the spring retainers 
on one side of the diffuser and let the diffuser face hang 
on its safety cords. See Figure 2.
The inlet spigot of the air diffuser backing box can be 
secured to the connecting duct by means of self-tapping 
screws or a blind rivets. For flush-mounting in fixed false 
ceiling constructions, secure the terminal by means of 
screws into place in the framework through either the 
sides or top of the diffuser backing box. The air diffuser 
and commissioning box in the version for low installation 
height must be centred and jointed together using the 
locking strip supplied. Secure the air diffuser in the cor-
rect position with self-tapping screws or pop rivets in the 
underside of the commissioning box. See Figure 4.
For mounting in modular false ceilings, it is advisable to 
select air diffusers with outer dimensions of 595 x 595 
mm. Position these directly down in the T-bar framework, 
and then secure them to the duct system or to the com-
missioning box.
If an ALS commissioning box is used, it must be secured 
to the building structure by means of hangers or mount-
ing brackets. 
The distance between the commissioning box and the 
air diffuser can be increased by as much as 500 mm with 
an ordinary circular duct without having to lengthen 
the measuring tubes and damper adjustment cords. See 
Figure 3.

Commissioning

Commissioning should be carried out with the air dif-
fuser face mounted. Pull the measuring tubes and damper 
adjustment cords out through the air diffuser face. Then 
connect the manometer to the correct measuring tube. 
For extract air, always use the transparent tube. The rated 
coefficient of performance of the air diffuser can be used 

Figure 1. Commissioning

in a calculation to determine the required commission-
ing pressure. Conclude commissioning by adjusting the 
damper to the correct blade position, tie a commissioning 
knot in the damper cords to indicate the damper position. 
See Figure 1.
The rated coefficient of performance (K-factor) is speci-
fied on the identification label of the product and in the 
relevant commissioning instructions at www.swegon.com.

Maintenance

The air diffuser can be cleaned, if necessary, using luke-
warm water with dishwashing detergent added or by 
vacuum cleaning using a brush nozzle. The duct system 
can be reached for cleaning after opening the air diffuser 
face. If a type ALS commissioning box is used, swing 
the air diffuser face to the side so that you can grip the 
damper tube by its handle and rotate it out of its holder. 
See Figure 5.

PELICAN CE

Tomelilla

Sweden

200-600

+ALS 160 -200/125 -200

k

k = XX / XX

q

FRÅ

NLU

FT /

 EXTR

ACT AI

R

k

p

q

=

k

p

q

=

(    )

2

p

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

Reviews: