3
20200910 Swegon reserves the right to alter specifications.
REACT
P
Rectangular design
Size WxH (mm)
Tube length
(meters)
Weight (kg)
Motor
Torque (Nm)
200 x 200
2
7.2
10
300 x 200
4
8.4
10
400 x 200
4
9.9
10
500 x 200
6
11.4
10
600 x 200
6
12.9
10
700 x 200
8
14.4
10
800 x 200
8
15.4
10
1000 x 200
12
18.4
10
300 x 300
4
10.9
10
400 x 300
4
12.4
10
500 x 300
6
13.9
10
600 x 300
6
15.4
10
700 x 300
8
16.8
10
800 x 300
8
18.4
10
1000 x 300
12
21.4
10
400 x 400
4
14.0
10
500 x 400
6
16.0
10
600 x 400
6
17.4
10
700 x 400
8
19.6
10
800 x 400
8
21.1
10
1000 x 400
12
24.2
10
1200 x 400
12
27.2
15
1400 x 400
16
30.3
15
1600 x 400
16
33.3
15
500 x 500
6
18.5
10
600 x 500
6
20.5
10
700 x 500
8
22.6
10
800 x 500
8
24.6
10
1000 x 500
12
28.6
15
1200 x 500
12
32.7
15
1400 x 500
16
36.8
15
1600 x 500
16
40.8
15
600 x 600
6
22.7
10
700 x 600
8
24.8
10
800 x 600
8
26.8
15
1000 x 600
12
30.9
15
1200 x 600
12
35.0
15
1400 x 600
16
39.2
15
1600 x 600
16
43.3
15
700 x 700
8
27.6
15
800 x 700
8
30.3
15
1000 x 700
12
34.9
15
1200 x 700
12
40.6
15
1400 x 700
16
45.7
15
H
B
104
20
220
20
20
Figure 6. Dimensions (mm), REACT P rectangular.
Installation – rectangular design
Dimension B in the figure and table below is found in the
table “Rectangular design” to the left.
NOTE! Damper spindles must be installed horizontally.
Straight section before REACT P in rectangular ducts
Type of disruption
E
One 90° bend
E = 2 x B
T piece
E = 2 x B
Figure 4. Straight section requirements and spacing, rectangular
ducts.
Figure 5. Straight duct section and spacing requirements, rec-
tangular REACT P and sound attenuator with baffle. Installation
with a straight duct section applies to both the supply air and the
extract air.
Straight duct section before/after REACT P – sound
attenuator with baffle
1
3
2
1. = Rectangular REACT P.
2. = Straight duct
≥
2xB.
3. = Sound attenuator with baffle.
1. Controller/Actuator always on the side of the rectangular damper.
E = Straight section.
W = Width, duct.
H = Height, duct.
1
Spacing at least 5xW
Spacing at least 5xW
Spacing at least 5xW
Straight duct section
at least 2xW