background image

REACT 

P

8

Swegon reserves the right to alter specifications.                           20200910

Technical data

IP class:

IP42

Corrosivity class:

C3

Pressure class:

A

Leakage classes according to SS-EN 1751

- Leakage class, casing:

C

- Leakage class circular damper, closed:

4

- Leakage class rectangular damper, 
closed:

3

Running times open/close (90°):

10 / 15 Nm:

150 s

Ambient temperature

Operation:

0 – +50 °C

Storage:

-20 – +50°C

RH:

10  -  95%                      

(non-condensing)

CE marking:

2006/42/EC (MD)

2014/30/EU (EMC)

2011/65/EU (RoHS2)

Electrical data

Power supply:

24 V AC/DC ±20% 50 - 60 Hz

Fixed connection cable, 
1000 mm with cable size.

4 x 0.75 mm

 2

2 x 0.38 mm

 2

Power consumption, for transformer rating:

REACT P 10 Nm

2.5 W

5.0 VA

REACT P 15 Nm

3.0 W

4.5 VA

Declaration of Conformity

Swegon AB hereby affirms that:
REACT P complies with the essential characteristic demands 
and relevant regulations specified in the directives, 
2006/42/EC (MD), 2014/30/EU (EMC) and 2011/65/EU 
(RoHS2):

The following standards have been observed:

EN ISO 12100:2010 

Safety of machinery - General principles for 
design - Risk assessment and risk mitigation

EN 60204-1:2006 

Safety of machinery - Electrical equipment of 
machines - Part 1: Generic standards

EN 60730-1:2011 

Automatic electrical controls for household 
and similar use - Part 1 Generic standards

EN 61000-6-2:2007 

Electromagnetic compatibility (EMC). Generic 
standards. Immunity for industrial environments

EN 61000-6-3:2007

Electromagnetic compatibility (EMC). Generic 
standards. Emission standard for residential, 
commercial and light-industrial environments

Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 200601 

This declaration is applicable only if the product has been 
installed according to the instructions in this document 
and if no modifications or changes have been made on 
this product.

References

www.swegon.com
Building Materials Declaration
REACT P Product data sheet
REACT Function Guide
REACT Modbus

Summary of Contents for REACT Pa

Page 1: ...n the damper blade rotates The product s actuator is equipped with a release button that permits manual control of the damper blade always ensure this is activated before working on the internal parts of the damper If the product is equipped with a spring return actuator there is no release button manual control is performed using the sup plied hex key where the damper blade is cranked to the requ...

Page 2: ...e frame of the building on each side of REACT P Figure 2 Spacing requirements circular ducts quantity Ø before and after the product 1 At least 5 x Ø after the damper supply air 2 At least 5 x Ø before the damper extract air 3 Examples of how spacing can be measured 4 Installation of measurement toppings 1 2 E 1 REACT P 2 FSR Clamp 80 3 6 0 Circular design Size ØD mm Tube length meters A mm B mm C...

Page 3: ...9 2 15 1600 x 600 16 43 3 15 700 x 700 8 27 6 15 800 x 700 8 30 3 15 1000 x 700 12 34 9 15 1200 x 700 12 40 6 15 1400 x 700 16 45 7 15 H B 104 20 220 20 20 Figure 6 Dimensions mm REACT P rectangular Installation rectangular design Dimension B in the figure and table below is found in the table Rectangular design to the left NOTE Damper spindles must be installed horizontally Straight section befor...

Page 4: ...n 0 10 and 2 10 V via the edit wheel Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax Pmax T Test est Mode Mode Adr Adr Pa Test inH O 10 3 x P n o m P n o m P r e s U n it P r e s U n it P m in P m in P m a x P m a x T T e s t e s t M o d e M o d e A d r A d r P a T e s t in H O 1 0 3 x Addr Used for Modbus for particulars on how to use Modbus see next page Pnom Pnom Pres Unit Pres Unit Pmin Pmin Pmax...

Page 5: ... 0 100 Addr Used for selecting communication settings for Modbus See table below Pnom Used for setting response delay for the Modbus communication see separate documents How to use Modbus Modbus tables are available in a separate document REACT Modbus m Display number EEPROM value Communication rate Parity Stop bits 13 0 1200 None 2 23 1 1200 Even 1 33 2 1200 Odd 1 4 3 2400 None 2 5 4 2400 Even 1 ...

Page 6: ...anized sheet steel Z275 Disposal Waste must be handled according to local regulations Product warranty The product warranty or service agreement will not be valid will not be extended if 1 the product is repaired modified or changed unless such repair modification or change has been approved by Swegon AB or 2 the serial number on the product has been made illegible or is missing Trouble shooting T...

Page 7: ... you know the value of the current pressure Pact Calculation of the current actual value U when you know the value of the current pressure Pact Key to formulas above Y control signal in V DC U actual value signal in V DC Pact current air pressure in Pa inH2 O 10 3 Pmin set min pressure in Pa inH2 O 10 3 Pmax set max pressure in Pa inH2 O 10 3 Performance checks Replacing the damper motor Figure 11...

Page 8: ... EU EMC and 2011 65 EU RoHS2 The following standards have been observed EN ISO 12100 2010 Safety of machinery General principles for design Risk assessment and risk mitigation EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 Generic standards EN 60730 1 2011 Automatic electrical controls for household and similar use Part 1 Generic standards EN 61000 6 2 2007 Electromagn...

Reviews: