FIRE DAMPER - FD
Possible damper orientations
Gypsum blocks wall
installation
Applique installation
frame
The wall is composed of gypsum blocks
(minimum density of 995 kg/m³), and with
minimum thickness of 70 mm.
1. Recommended wall opening for the fire damper
installation is B (H) + 80 mm.
Damper blade must be closed during installation!
2. Insert fire damper into wall and fasten with screws
(4 pcs, 4,8x60 mm).
Test the operation of the damper blade!
2
1
INSTALLATION
Always e
nsure the damper is sufficiently supported