43
FIRE DAMPER - FD
Possible damper orientations
Battery assembly
installation
1x2
The wall is composed of blocks of aerated concrete
(minimum density 550 kg/m³) and with a minimum
thickness of 100 mm.
*For battery installation 1x2 use 2x connecting
frame.
Installation only possible with FD40!
2
1
4
3
(1)
Accessories
(2)
Type
(3)
Length
FD-A
-
CF60
- 800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60
- Connecting frame 60 mm
CF100
- Connecting frame 100 mm
(3)
Connecting frame length
200 ... 1500 [mm]
INSTALLATION
1. Prepare a hole of dimensions
B + 80 mm and 2H + Connecting
frame width (CF60/CF100) + 80 mm.
Fix the dampers to the wall using the
screws.
Damper blade must be closed
during installation!
2. Place the installation kit to
the dampers. Attach the installation
kit to the dampers using the self-
tapping screws every 150 mm.
3. Fill the space between the
dampers with mineral wool
(100 kg/m³ of density).
4. Fill the space between the
dampers and the wall with mortar.
Test the operation of the damper blade!
2
1
4
3
- mineral wool
- mortar
Always e
nsure the damper is sufficiently supported