51
FIRE DAMPER - FD
ELECTRIC
ACTUATOR
SCHISCHEK ExMax
Damper is delivered in closed position.
When electric actuator is connected to the
power supply damper will open. When the damper
reaches the end position(damper open), in which it
is
blocked, the electric actuator will stop. Closing
fire damper takes place automatically when a
power failure occurs. Thermal tripping device that
comes with fire damper causes power circuit break
at a temperature of 72 °C (inside or outside duct).
If checking is needed for proper functioning of fire
damper, pushing the switch on the thermal tripping
device will close damper. When switch on tripping
device is released, the damper will open.
Damper can be opened without connecting to a
voltage with enclosed Allen key, by turning in the
direction of the arrow on electric actuator (clockwise).
After release of Allen key, damper will go to closed
position.
1)
Tecnical documentation Safety temperature
2)
Tecnical documentation electric actuator
Schischek ExMax-5.10-BF
3)
Tecnical documentation Ex-e terminal box
ACTUATORS
1
2
3
Wiring diagram
Technical specifications
Type
ExMax -5.10-BF
Torque
5/10 Nm
Power Supply
24-230 V AC/DC
Running time
3/15/30/60/120 s / 90°
Spring return
3 or 10s / 90°
Control mode
On-Off, 3 position
Feedback
2 x aux sw Ex. tripping
device
Ambient temperature range min. -40 °C, max. 40 °C
Ambient humidity
0-90% r.h.,
non-condensing
Service life
Min. 10,000 cycles @ 10 s,
min 1000 cycles @ 1s
Maintenance
Maintenance-free
Weight
3,5 kg
24...240 VAC/DC