FIRE DAMPER - FD
17
Range
Supporting
construction
Type of installation
Wall
thickness
Supporting construction
details
Classification
Tested
under pressure
Details
FD25 & FD40
Rigid wall
Gypsum plaster/Mortar
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m³)
Reinforced concrete
(≥ 2200 kg/m³)
EI 120 (ve i
↔
o)S
500Pa
Mineral wool and cover boards
EI 90 (ve i
↔
o)S
500Pa
Fire Batt/Weichschott
300Pa
Flexible wall
Gypsum plaster/Mortar and
cover boards
≥ 70 mm
Gypsum blocks
(≥ 995 kg/m³)
EI 120 (ve i
↔
o)S
500Pa
Gypsum plaster/Mortar and
cover boards
≥ 100 mm
A: Plasterboard
type F (EN520),
mineral wool up to
100 kg/m³
B: Plasterboard
type A (EN520),
mineral wool up to
60 kg/m³
A: EI 120 (ve i
↔
o)S
B: EI 60 (ve i
↔
o)S
500Pa
Mineral wool and cover boards
A: EI 90 (ve i
↔
o)S
B: EI 60 (ve i
↔
o)S
500Pa
Fire Batt/Weichschott
A: EI 90 (ve i
↔
o)S
B: EI 60 (ve i
↔
o)S
300Pa
Floor/ceiling
Gypsum plaster/Mortar
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m³)
Reinforced concrete
(≥ 2200 kg/m³)
EI 120 (ho i
↔
o)S
500Pa
Fire Batt/Weichschott
EI 90 (ho i
↔
o)S
300Pa
APPLIQUE INST
ALLA
TION FRAME
FD25 APP
100x200 till 800x600
mm
Rigid wall
APPLIQUE (installation frame)
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m³)
Reinforced concrete
(≥ 2200kg/m³)
EI 90 (ve i
↔
o)S
500Pa
Flexible wall
APPLIQUE (installation frame)
≥ 70 mm
Gypsum blocks
(≥ 995 kg/m³)
EI 90 (ve i
↔
o)S
500Pa
APPLIQUE (installation frame)
≥ 100 mm
Plasterboard
type F (EN520)
EI 90 (ve i
↔
o)S
500Pa
MF1/ MF2 INST
ALLA
TION FRAME
FD25 MF1
100x200 till 800x600
mm
FD25 MF2
100x200 till 800x600
mm (only shaft wall!)
FD40 MF2
800x600 till 1500x800
mm
Rigid wall
MF1/MF2 (installation frame)
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m³)
Reinforced concrete
(≥ 2200kg/m³)
FD25: EI 60 (ve
i↔
o)S
500Pa
FD40: EI 90 (ve i
↔
o)S
Flexible wall
MF1/MF2 (installation frame)
≥ 70 mm
Gypsum blocks
(≥ 995 kg/m³)
FD25: EI 60 (ve i
↔
o)S
500Pa
FD40: EI 90 (ve i
↔
o)S
Flexible wall
MF1/MF2 (installation frame)
≥ 100 mm
Plasterboard
A:type A (EN520)
B:type F (EN520)
A:FD25: EI 60 (ve i
↔
o)S
500Pa
B:FD40: EI 90 (ve i
↔
o)S
Floor/ceiling
MF1/MF2 (installation frame)
≥ 100 mm
Aerated concrete
( ≥ 550 kg/m³)
Reinforced concrete
(≥ 2200 kg/m³)
FD25: EI 120 (ve i
↔
o)S
FD40: EI 90 (ve i
↔
o)S
300Pa
Flexible wall
MF2 (installation frame)
≥ 90 mm
Shaft wall
(steel frame)
FD25: EI 90 (ve i
↔
o)S
FD40: EI 90 (ve i
↔
o)S
500Pa
FIRE DAMPER - FD
Check for more information about certificate
installations in the declaration of performance:
Aerated concrete ( ≥ 550 kg/m
3
) or
reinforced concrete (≥ 2200 kg/m
3
)
wall, more than 100 mm thick
Gypsum blocks (≥ 995 kg/m³) wall,
more than 70 mm thick
Plasterboard wall, type F (EN520),
Plasterboard wall, type A (EN520),
more than 100 mm thick
Aerated concrete ( ≥ 550 kg/m³) or
reinforced concrete (≥ 2200 kg/m³)
ceiling / floor, more than 100 mm thick
Shaft wall, steel frame construction
INSTALLATION
Gypsum plaster, mortar sealing od
mortar and cover boards
Sealing with mineral wool and cover
boards
Sealing with mineral wool and
fireproof coating - FireBatt
Applique installation
MF1/MF2 installation
Remote from wall installation
Battery installation