GB.TBLZ66.110620

Swegon reserves the right to alter specifications.

www.swegon.com     1

1. General

The TBLZ-1-66 accessory is a control system incorporated 
into a control box. The control box is designed for installa-
tion in connection with the GOLD air handling units.

Communication cables for Modbus communication 
should be connected between the control box and the 
GOLD air handling units.

The control box contains a Programmable Logic Control-
ler system and its front panel has a control terminal with a 
display screen.

The buttons and display screen are used for entering set-
tings and viewing readings for common functions. 

2. Range of application

The TBLZ-1-66 control box is a control system for control-
ling two parallel GOLD air handling units. 

One GOLD air handling unit is selected as the Master, and 
the other unit is selected as the Slave.

The control box transmits set points to both air handling 
units. These set points then control each unit separately. 

If the air handling units are to be regulated on a VAV basis 
and the duct pressure is to be kept constant, connect a 
standard pressure sensor to the GOLD unit that operates 
as the Master. The pressure readings are transmitted via 
the communication system to the control box and are 
processed there. This also applies to the external room 
temperature sensor and the CO

2

 sensor, if one is used in 

the system.

Conditions

Parallel control is possible for the size 04–80 GOLD air 
handling units.

The GOLD air handling units involved must be of the same 
size.

The air handling units are considered parallel if they are 
connected to a common duct system.

Both air handling units must be equipped with the same 
accessories, such as an air heater, air cooler, dampers, etc.  

Installation instructions for the TBLZ-1-66 control box for 
controlling two air handling units (Twin Function)
GOLD 04-80

3. Installation

The control box should be installed in connection with the 
GOLD unit selected as the Master.

It is advantageous if the control box panel and the hand-
held micro terminal of the Master air handling unit are 
located in such a way that they can be operated and 
supervised from the same place.

4. Technical data

Enclosure class 

IP 66 

 

Ambient temp. 

0 - +50°C 

for a rel. hum. of 

5 - 85% (non-condensing) 

Weight 

7 kg

Dimensions   

 380x300x220 
(WidthxHeightxDepth) 

Summary of Contents for TBLZ-1-66

Page 1: ...to be kept constant connect a standard pressure sensor to the GOLD unit that operates as the Master The pressure readings are transmitted via the communication system to the control box and are proce...

Page 2: ...ling units 7 1 Temperature regulation ERS and Supply air regulation ERS and supply air regulation are controlled in each GOLD unit The settings in the control box are automatically transmitted over to...

Page 3: ...d for moving the cursor in the dis play The D buttons are number buttons and are used for enter ing values 8 2 Menus in the display 8 2 1 Main menu The uppermost text line shows the type of air handli...

Page 4: ...current extract air set point for extract air regulation in the control box The value for OUTDOORS shows the current outdoor tem perature of the relevant air handling unit PREV For returning to the n...

Page 5: ...setting the total airflow from both air handling units In the display image to the right SA is shown as pressure regulation and EA as flow regulation If flow regulation is used the control system of t...

Page 6: ...w appears offering possible alternatives Select the desired type of regulation and confirm by pressing the Enter button BACK For returning to the next higher level To set the communication means with...

Page 7: ...horization level 3 in order to obtain authorization for changing temperature and flow regula tion functions Press the Log In button enter the digits 1111 Then press the Enter button A confirmation wil...

Page 8: ...GB TBLZ66 110620 Swegon reserves the right to alter specifications 8 www swegon com...

Reviews: