GB.TBLZ66.110620
Swegon reserves the right to alter specifications.
4 www.swegon.com
LOG IN:
Opens the Authorization level. Requires that you
enter a code.
LOG OUT:
Closes the Authorization level.
8.2.3 Temperature
PREV:
For returning to the next higher level.
READ:
For reading temperatures.
SET:
For setting temperature set points.
Readings
For reading current temperatures in the Master unit (Unit
1) and the Slave unit (Unit 2).
The first value for SA shows the current supply air tem-
perature of each air handling unit, the second value shows
the current supply air set point of each air handling unit.
The first value for EA shows the current extract air tem-
perature of each air handling unit, the second value shows
the current extract air set point (for extract air regulation)
in the control box.
The value for OUTDOORS shows the current outdoor tem-
perature of the relevant air handling unit.
PREV:
For returning to the next higher level.
Setting
PREV:
For returning to the next higher level.
CTRL:
For setting the temperature controller parameters.
Temperature controller
PREV:
For returning to the next higher level.
Temperature
PREV.
READ
SET
Temperature
AHU 1
AHU 2
SA
22.4°C/30.0°C 26.7°C/30.0°C
EA
21.9°C/23.0°C 27.1°C/23.0°C
OUTD 22.2°C
27.4°C
PREV.
Temperature set points
ROOM 23.0°C
Min. limit.
14.0°C
Max. limit.
30.0°C
PREV.
For setting of extract air temperature set points.
PREV.
REG.
For setting of supply air temperature set points.
Temperature set points
Supply air
30.0°C
PREV.
PREV.
REG.
For setting the temperature controller parameters:
Prop factor Xp/Fp 50.00
I-time
60.0 sec.
Ctrl. deviation 10.7 K
Output signal 29.96°C
PREV.
PREV.