background image

GB.TBLZ66.110620

Swegon reserves the right to alter specifications.

www.swegon.com     5

REG. EA

REG.

SA

8.2.4 Flow/Pressure
PREV:

   For returning to the next higher level.

READ:

  For reading the current flows/pressures. 

SET:

 

For setting flow/pressure set points.

Readings

For reading the current flows or pressures.

In the display image to the right, SA is shown as pressure 
regulation and EA as flow regulation.

The first value for SA shows the current pressure; the 
second value shows the current pressure set point.

The first value for EA shows the total airflow from both air 
handling units; the second value shows the current flow 
set point.

PREV:

   For returning to the next higher level.

Setting

For setting the desired pressure in the common duct, or 
for setting the total airflow from both air handling units. 

In the display image to the right, SA is shown as pressure 
regulation and EA as flow regulation. 

If flow regulation is used, the control system of the control 
box splits the airflow into two equal set points, one for 
each air handling unit.

PREV:

    

For returning to the next higher level.

CTRL. SA:

 

 For setting the parameters for the supply 
air fan flow controller. 

CTRL. EA:

 

 For setting the parameters for the extract 
air fan flow controller.

Flow/Pressure

PREV.

READ

SET

SA 

-142 Pa/ 

200Pa

EA 

01/s/ 01/s

PREV.

Flow/Pressure

SA 

200 Pa/ 

EA low 

300 l/s

SA max 

1,000 l/s 

EA high 

600 l/s

  

 

EA min 

3,500 l/s

  

 

EA max 

24,000 l/s

PREV.

Pressure setting

For setting the flow controller parameters.

Prop factor Xp/Fp  50.00

I-time 

  30.0 sec.

D-time 

  1.0 sec.

Ctrl. deviation    34.2 K

Output signal    1,500 l/s

PREV.

PREV.

For setting the desired pressure in the duct, or for setting the total air-
flow from both air handling units.

Summary of Contents for TBLZ-1-66

Page 1: ...to be kept constant connect a standard pressure sensor to the GOLD unit that operates as the Master The pressure readings are transmitted via the communication system to the control box and are proce...

Page 2: ...ling units 7 1 Temperature regulation ERS and Supply air regulation ERS and supply air regulation are controlled in each GOLD unit The settings in the control box are automatically transmitted over to...

Page 3: ...d for moving the cursor in the dis play The D buttons are number buttons and are used for enter ing values 8 2 Menus in the display 8 2 1 Main menu The uppermost text line shows the type of air handli...

Page 4: ...current extract air set point for extract air regulation in the control box The value for OUTDOORS shows the current outdoor tem perature of the relevant air handling unit PREV For returning to the n...

Page 5: ...setting the total airflow from both air handling units In the display image to the right SA is shown as pressure regulation and EA as flow regulation If flow regulation is used the control system of t...

Page 6: ...w appears offering possible alternatives Select the desired type of regulation and confirm by pressing the Enter button BACK For returning to the next higher level To set the communication means with...

Page 7: ...horization level 3 in order to obtain authorization for changing temperature and flow regula tion functions Press the Log In button enter the digits 1111 Then press the Enter button A confirmation wil...

Page 8: ...GB TBLZ66 110620 Swegon reserves the right to alter specifications 8 www swegon com...

Reviews: