8.2.5 To select temperatures and flow functions
The operator must log in onto Authorization level 3 in
order to be able to change the functions for temperature
or flow regulation, see Section 8.2.6.
PREV:
For returning to the next higher level.
FUNCTIONS:
For setting temperatures and flow func-
tions.
COMMUNICAT:
For setting the parameters for commu-
nication with a main control system.
For selecting temperatures and fan functions.
The form of regulation for temperature regulation or flow/
pressure regulation can be selected by moving the cursor
to the relevant control configuration. When you press the
Enter button, a new window appears offering possible
alternatives. Select the desired type of regulation and
confirm by pressing the Enter button.
BACK:
For returning to the next higher level.
To set the communication means
with the main control system
For selecting the communication system.
PREV:
For returning to the next higher level.
Ethernet:
For setting the Ethernet parameters.
Modbus:
For setting the Modbus parameters.
To set Ethernet communication
To set the IP-address, netmask and gateway for Ethernet
communication.
PREV:
For returning to the next higher level.
To set Modbus communication
PREV:
For returning to the next higher level.
DIAGN.:
Diagnostic of internal Modbus communi-
cation
FUNC
TIONS
COMMU
NICAT
PREV.
Temp.reg.
Flow/Pressure
ERS Regulation 1
SA fan
Flow regulation
EA fan
Flow regulation
BACK
Communication
Mod-
bus
Ether
net
PREV.
IP address: 192.168.000.001
Netmask: 255.255.255.000
GateWay: 000.000.000.000
PREV.
PREV.
DIAGN.