background image

The document was originally written in Swedish.

Application area

The product is a flow commissioning damper or constant 
flow damper with integrated radio transmitter designed 
for comfort ventilation indoors within Swegon’s system for 
demand-controlled ventilation WISE. The product is used to 
regulate the supply air flow in the ventilation duct. 
The product may not be used for anything other than its 
intended use.

General

Read through the entire instructions for use 
before you install/use the product and save the 
instructions for future reference. It is not permis-
sible to make changes or modify this product 
other than those specified in this document.

The packaging contains the following 
items:

1 x WISE Colibri C
1 x Instructions for use

Protective equipment

Always use appropriate personal protective 
equipment for the work in question, in the 
form of gloves, respirators and protective 
glasses during handling, installation, cleaning 
and service/maintenance.

Electrical safety

Permitted voltage, see “Electrical data”.
It is not permissible to insert foreign objects 
into the product’s contactor connections 
or the electronics's openings; risk for short 
circuiting.

24 V isolation transformer to be connected should comply 
with the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the 
product and the power supply source.
Disconnect the power supply when working on products 
that are not required to run in production.
Always follow the local/national rules for who shall be 
permitted to carry out this type of electrical installation.

WISE 

Colibri Ceiling a

Instructions for Use

20181012

Art. 1546012

Symbol key

Symbols on the machine.

This product complies with applicable EU direc-
tives

Symbols in this user manual

Warning/Caution!

Risk of crushing

Summary of Contents for WISE Colibri Ceiling a

Page 1: ... personal protective equipment for the work in question in the form of gloves respirators and protective glasses during handling installation cleaning and service maintenance Electrical safety Permitted voltage see Electrical data It is not permissible to insert foreign objects into the product s contactor connections or the electronics s openings risk for short circuiting 24 V isolation transform...

Page 2: ...g Install the product for easy access during service main tenance If the product is mounted in a fixed ceiling the inspec tion hatch must be located so that the product is acces sible for inspection If the product is mounted in cold areas the commis sioning box must be insulated on the outside against condensation The product must be installed horizontally It is recommended to mount the product so...

Page 3: ...gure 1 WISE Colibri C measurement figure Figure 2 Straight section requirements circular ducts 1 3 Quantity Ø before the product 0 x Ø 4 Quantity Ø before the product 1 x Ø 5 Quantity Ø before the product 2 x Ø Cleaning hatch 1 2 3 4 5 Installation WISE Colibri C s air flow measurement requires a straight section before the product in the air direction according to the installation figures 3 20181...

Page 4: ... Orange Alternating RJ9 Damper connection rear side Temp sensor Damper connection front side Pressure tube red Pressure tube blue Motor Tolero damper WISE SMB Sensor Module Basic LED see table LED Explanation LED see table LED Explanation RJ45 Valve actuator accessory see Connection example WISE Colibri C 24V AC Onward connec tion of the sup ply terminals 2 and 3 are parallel Connection example WI...

Page 5: ...nt or a vacuum cleaner Internal cleaning The damper insert must be dismantled when cleaning the ventilation system Cleaning equipment such as whisks and the like must not be fed through the damper insert If necessary remove dust and other particles that can be present in the product Never use detergent and cleaning solvent or a vacuum cleaner Service maintenance The product does not require any ma...

Page 6: ...e 5 Open damper front with Quick Access Suspension of WISE Colibri C and connection of WISE SMB Figure 4 Suspension of WISE Colibri C connection of WISE SMB WISE Colibri Ceiling 6 Swegon reserves the right to alter specifications 20181012 ...

Page 7: ...suring tubes and cables from WISE CU Pull WISE CU downwards and angle out from the holder Dismantling the damper insert Figure 6 Dismantling the damper insert Reassemble in the reverse order Disconnect the measuring tubes and damper motor cable Fold away the perforated mesh Turn the damper insert so that the bayonet fitting releases Pull out the damper insert 7 20181012 Swegon reserves the right t...

Page 8: ...or electric actuators IEC 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code EN 61000 6 2 2007 Electromagnetic compatibility EMC Generic standards Immunity for industrial environ ments EN 61000 6 3 2007 Electromagnetic compatibility EMC Generic standards Emission standard for residential commercial and light industrial environments EN 300328 V1 9 2 V1 9 1 V1 8 1 Electromagneti...