Page | 10
Warning:
o
For standard battery pack, there is one DC breaker to disconnect the battery
pack and the UPS. But for other external battery pack, make sure a DC breaker
or other protection device between UPS and external battery pack is installed.
If not, please install it carefully. Switch off the battery breaker before
installation.
NOTE:
Set the battery pack breaker in “OFF” position and then install the battery
pack.
o
Pay highly attention to the rated battery voltage marked on the rear panel. If you
want to change the numbers of the battery pack, please make sure you modify
the setting simultaneously. The connection with wrong battery voltage may
cause permanent damage of the UPS. Make sure the voltage of the battery pack
is correct.
o
Pay highly attention to the polarity marking on external battery terminal block,
and make sure the correct battery polarity is connected. Wrong connection may
cause permanent damage of the UPS.
o
Make sure the protective earth ground wiring is correct. The wire current spec,
color, position, connection and conductance reliability should be checked
carefully.
o
Make sure the utility input & output wiring is correct. The wire current spec,
color, position, connection and conductance reliability should be checked
carefully. Make sure the L/N site is correct, not reverse and short-circuited.
2.6.
UPS Installation for Parallel System
If the UPS is only available for single operation, you may skip this section to the
next.
1)
Install and wires the UPSs according to the section 2.3.
2)
Connect the output wires of each UPS to an output breaker.
3)
Connect all output breakers to a major output breaker. Then this major output
breaker will directly connect to the loads.