Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-
100%.
3.4.
Audible Alarm
DESCRIPTION
BUZZER STATUS
MUTED
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every second
Yes
Others
Beeping once every second
Fault
All
Beeping continuously
Yes
3.5.
Single UPS Operation
3.5.1.
Turn on the UPS with utility power supply (in AC mode)
1)
After power supply is connected correctly, set the breaker of the battery pack at
“ON” position (the step only available for long-run model). Then set the input
breaker at “ON” position. At this time the fan is running and the UPS enter to
power on mode for initialization, several seconds later, UPS operates in Bypass
mode and supplies power to the loads via the bypass.
NOTE:
When UPS is in Bypass mode, the output voltage will directly power from utility
after you switch on the input breaker. In Bypass mode, the load is not protected by UPS.
To protect your precious devices, you should turn on the UPS. Refer to next step.
2)
Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will
beep once.
3)
A few seconds later, the UPS will enter to AC mode. If the utility power is
abnormal, the UPS will operate in Battery mode without interruption.
NOTE:
When the UPS is running out battery, it will shut down automatically at Battery
mode. When the utility power is restored, the UPS will auto restart in AC mode.