Page | 22
2)
Turn off the output breaker of this unit, and then turn off the input breaker of
this unit.
3)
After it shuts down, you can turn off the battery breaker (for long-run model)
and remove the parallel cable and share current cable. Then, remove the unit
from the parallel system.
Second method:
1)
If the bypass is abnormal, you can not remove the UPS without interruption. You
must cut off the load and shut down the system.
2)
Make sure the bypass setting is enabled in each UPS and then turn off the
running system. All UPS will transfer to bypass mode. Remove all the
maintenance bypass covers and set the maintenance switches from “UPS” to
“BPS”. Turn off the input breakers and battery breakers.
3)
Remove the UPS that you want.
4)
Turn on the input breaker of the remaining UPSs and the system will transfer to
Bypass mode.
5)
Set the maintenance switches from “BPS” to “UPS and put the maintenance
bypass covers back. Turn on the remaining UPSs and finish the parallel system
connection.
Warning:
(Only for the parallel system)
o
Before turning on the parallel system to activate inverter, make sure
that all
unit’s maintenance switch at the same position.
o
When parallel system is turned on to work through inverter, please do
not operate the maintenance switch of any unit.