18
INTERFACE
SETTING
Parameter 3: Enable or disable Bypass function.
ENA: Bypass mode enable.
DIS: Bypass mode disable (Default).
07:
Bypass voltage range setting.
INTERFACE
SETTING
Parameter 2 & 3: Set the acceptable high voltage
point and acceptable low voltage.
Press the Down key or Up key to set.
HLS: Bypass high voltage point.
For 208/220/230/240 VAC models:
235-264: setting the high voltage point from
235Vac to 264Vac
(Default: 264Vac).
For 110/115/120/127 VAC models:
125-132: setting the high voltage point from
115Vac to 132Vac
(Default: 132Vac).
LLS: Bypass low voltage point.
184-225: setting the low voltage point from
184Vac to 225Vac
(Default: 195Vac).
For 110/115/120/127 VAC models:
98-115: setting the high voltage point from
98Vac to 115Vac
(Default: 98Vac).
08:
Autonomy limitation setting
INTERFACE
SETTING