19
Parameter 3: Set up backup time on battery mode
for general outlets.
0-999: setting the backup time in minutes from 0-999
for general outlets on battery mode.
0: When setting as “0”, the backup time will be
only 10 seconds.
999: When setting as “999”, the backup time
setting will be disabled. (Default)
00:
Exit setting
3.6. Operating Mode Description
OPERATING
MODE
DESCRIPTION
LCD DISPLAY
Online mode
When the input voltage is within acceptable
range, UPS will provide pure and stable AC
power to output. The UPS will also charge the
battery at online mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass voltage to
output for energy saving.
Frequency
Converter mode
When input frequency is within 40 Hz to 70 Hz,
the UPS can be set at a constant output
frequency, 50 Hz or 60 Hz. The UPS will still
charge battery under this mode.
Battery mode
When the input voltage is beyond the
acceptable range or power failure and alarm is
sounding every 4 second, UPS will backup
power from battery.
Bypass mode
When input voltage is within acceptable range
but UPS is overload, UPS will enter bypass
mode or bypass mode can be set by front panel.
Alarm is sounding every 10 second.