background image

PROBLEM

SOLUTION

The unit will not start.  

Display alternates “rP” with the 

“DISPLAY / PROGRAM’ switch 

value.

The voltage inputs are reverse phased.  If this is the initial start 

up, swap the “L1” and “L3” leads to correct the problem.  If the 

overload relay has been previously running, the power system 

has been reverse phased.  Check the phase sequence of the 

incoming power lines.

The unit will not start.  

Display alternates “SP”, “uB”, 

“HI”, or “Lo with “DISPLAY / 

PROGRAM” switch parameter 

value.

The incoming voltage is not within the limits programmed in the 

“VUB”, “HV”, and “LV” settings.  Adjust the “DISPLAY / 

PROGRAM” switch to read the incoming line voltage values.  

Correct the incoming power problem and check programmed 

limits to verify they are correct.

Display alternates “SP”, “uB”, 

or “oc” with “RUN”.

The overload relay has tripped on the fault shown on the display 

and is timimg down “RD2” before restarting.

Display alternates “uc” with 

“RUN”.

The overload relay has tripped on undercurrent and is timing 

down “RD3” before restarting.  If undercurrent is not a normal 

condition for this installation, check for broken shafts, broken 

belts, etc.

Display is showing a solid “SP”, 

“uB”, or “oc”.

The unit has tripped on the fault shown and manual reset is 

required because of the programmed setting in”#RF”.  Check 

the system for problems that would produce the single phase, 

overload, or current unbalance fault like a jam.

Display is showing a solid “uc”.

The unit has tripped on undercurrent and a manual reset is 

required because of the setting in “#RU”.  Check the system for 

problems that would produce a loss of load like a broken belt or 

a pump is out of liquid.

Display is showing a solid “CF”.

The unit has tripped on a single phasing of the current, but was 

not single phased by the incoming power.  Check for damaged 

contacts or loose wiring.

TROUBLESHOOTING

Any questions or comments call SymCom at 1-800-843-8848 or 

1-605-348-5580

07/25/03 

 

 

 

                 -12-

Summary of Contents for 777-575-FT

Page 1: ...t motor conductor i e the A phase conductor should go through the A round hole See Figure 1 for a typical wiring diagram 2 2 For amperages less than 26 amps loop the motor conductors according to Tabl...

Page 2: ...IAGRAM FOR 26 90 FLA FULL LOAD AMPS NUMBER OF LOOPS NUMBER OF CONDUCTORS THROUGH A B and C MULT PROGRAM SETTING 2 0 2 5 9 10 10 2 6 3 0 8 9 9 3 1 3 5 7 8 8 3 6 4 0 6 7 7 4 1 5 0 5 6 6 5 1 6 0 4 5 5 6...

Page 3: ...RMS 600 VAC MAX SYMCOM INC 800 243 8848 RAPID CITY SD IND CONT EQ LISTED 784X LR46510 L1 L2 L3 NO C NC MODEL 777 FT OVERLOAD RELAY 20 90A RESET PROGRAM RD3 RF VUB OC RU ADDR MULT RD2 KWS HV LKW RD1 C...

Page 4: ...GRAM adjustment is between approximately 7 O Clock and 11 O Clock Likewise the ADDR setting will only be programmed when the DISPLAY PROGRAM adjustment is between approximately 11 O Clock and 5 O Cloc...

Page 5: ...ection for the application All parameters are actual values except the VUB and CUB settings which are percentages The range these parameters can be programmed to is found in the specifications at the...

Page 6: ...consulted for OC settings However OC is typically between 110 and 125 of Full Load Amperage FLA UC The UC undercurrent setting is typically set to 80 of full load amperage FLA The overload relay with...

Page 7: ...rip mode TC J00 the RD1 position becomes the motor acceleration time To view and adjust MA TC must be J00 The motor acceleration time is related to the load on a motor For high inertia loads such as f...

Page 8: ...The following settings are available 0 1 oc1 2 oc2 3 oc3 4 oc4 A and ocA A setting which includes oc will allow the overload relay to automatically reset after an overload fault eg a setting of oc2 w...

Page 9: ...bled 1 minute after the motor starts and provides a 2 second trip time for motors exceeding 400 SFA regardless of trip class J00 Fast Linear Trip Mode This setting provides an adjustable linear trip t...

Page 10: ...s that 1 start attempt usually clears the sand out of the impeller RF oc1 UCTD UCTD 10 GF Because it may take several days to get a new pump motor and schedule for maintenance personnel to remove and...

Page 11: ...label The multi function display also announces system faults such as low voltage high voltage single phasing unbalance and reverse phasing errors Any time the MODE SELECT switch is in the RUN positio...

Page 12: ...img down RD2 before restarting Display alternates uc with RUN The overload relay has tripped on undercurrent and is timing down RD3 before restarting If undercurrent is not a normal condition for this...

Page 13: ...computer Control and monitoring is also possible from SymCom s RM 1000 and RM 2000 PLC and SCADA systems using the RS 485 standard and MODBUS protocol can also be used NOTE An RS 485MS 2W module is r...

Page 14: ...ust the Display Program adjustment until cLr appears on the display Release the Reset Program Button To verify the last fault was cleared place the Mode Select switch in the Run position Then press an...

Page 15: ...urrent 15 Timing 5 1 second Repeatability Voltage 0 5 of nominal voltage Current 1 of nominal current TRIP TIMES Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpo...

Page 16: ...Compliance to a Level of 6 KV Line to Line Hi Potential Test Meets UL508 2 x Rated Voltage 1000 Volts for 1 Minute Vibration IEC 68 2 6 10 55 Hz 1 mm Peak to Peak 2 Hours 3 Axis Shock IEC 68 2 27 30...

Page 17: ...h 0 315 Seconds RD2 Motor Cool Down Timer 2 500 Minutes x 0 5 if TC J00 OCTD Overcurrent Trip Delay Linear 2 250 x 0 158 0 315 Seconds RD3 Dry Well Recovery Timer 2 500 Minutes x 0 5 if TC J00 RU Numb...

Page 18: ...DISPLAY MESSAGE RESET PROGRAM 800 843 8848 SYMCOM INC RAPID CITY SD DIMENSIONS 07 25 03 18...

Page 19: ...sions 18 Fast Linear Trip Mode 5 Multi Function System Display 11 Operation 2 Programmable Operationg Points 17 Programming Examples 9 Programmable Parameters 5 Programming 4 Remote Reset 13 Specifica...

Page 20: ...2880 North Plaza Drive Rapid City SD 57702 Phone 800 843 8848 or 605 348 5580 FAX 605 348 5685 Visit our website at www symcom com for our complete catalog and new product listings...

Reviews: