background image

 

4 - 

 

1/05 

 

PROGRAMMABLE PARAMETERS 

 
The following settings MUST be programmed by the user in order to provide proper protection for 
the application. All parameters are actual values except for the VUB and CUB settings; these are 
programmed as percentages. The range each parameter can be programmed to is found on the 
electrical specifications table on page 13. See page 8 for programming examples.  

 
LV/HV 

-   The recommended settings for LV (low voltage) and HV (high voltage) according to the 

NEMA MG1 standard are ±10% of the motors nameplate voltage. For other settings, the 
motor manufacturer should be contacted. 

Example:

 The motor nameplate voltage is 230 volts. 90% and 110% of 230 is 0.9 x 

230=207 volts for the LV setting and 230 x 1.1=253 volts for the HV setting. These 
parameters are based on the average voltage going to the motor. 

 

VUB/TS 

- VUB (voltage unbalance) is factory set at 6%. The NEMA MG1 standard says a motor 

should not be operated above a 1% voltage unbalance without derating

 

the motor. Most 

utility supplied power sources have a difficult time sustaining a 1% VUB. The motor 
manufacturer should be consulted for an exact VUB setting. A setting of 999 for VUB will 
disable the VUB protection but will not disable SP (single-phase protection). 
The VUB is calculated as follows: 
%VUB = [(Maximum deviation from the average)/Average] x 100% 

Example: 

Measured line-line voltages = 203, 210, and 212, so the average = 

(203+210+212)/3 = 208.3, the maximum deviation from the average is the biggest 
difference between the average voltage (208.3) and any one voltage reading, 212-
208.3 = 3.7, 210-208.3 = 1.7 and 208.3-203 = 5.3, therefore the maximum deviation 
from the average is 5.3. The VUB is then = 5.3/208.3 x 100= 2.5%. 

 

The TS setting allows the user to turn the temperature sensor trip function on or off. 

 
MULT 

-   MULT (multiplier) setting is found on Table 1. The MULT setting is determined by the 

current the unit will be monitoring. This allows the unit to display the correct current. 
Changing this setting will also change the UC, OC, and GF setpoints.  

 

OC

-  

OC (overcurrent) is usually set at the service factor amperage (typically 100-115% of 
motor FLA) of the motor, which is determined by the motor manufacturer. If any one leg of 
current exceeds the OC setting, the unit will follow its overload trip curve (see Figure 4). 

 
UC 

-  

UC (undercurrent) is typically set at 80% of the full-load amperage of the motor. This is 
usually adequate for protection of loss of load for many pumps and motors, including 
submersibles. If the motor is not pulling near full load amperage then the UC may have to 
be set to something higher than 80% of FLA for adequate protection. UC can be set to 0 if 
UC protection is not desired. The UC trip point examines average current to determine if 
an undercurrent trip condition exists. 

 

CUB 

-  

CUB (current unbalance) is factory set to 7%. SymCom recommends the motor 
manufacturer be contacted for an exact setting. The CUB is calculated the same way the 
VUB is determined above. The CUB protection can be disabled by programming a 999 in 
this setting. This will disable current unbalance protection and current single phasing 
protection. 

 

TC 

-  

TC (trip class) is the parameter used to determine when the unit will trip when an overload 
condition is detected. For standard motors, the TC is typically set at 20. The motor 
manufacturer should be contacted for exact TC settings. Table 2 and Figure 4 show the 
TC settings and trip times. 

Summary of Contents for 777-TS

Page 1: ...perages from 26 90 amps insert the motor conductors through the holes marked A B and C Make certain the conductor through each hole corresponds to the right motor conductor i e the A phase conductor s...

Page 2: ...XTERNAL CTs REQUIRED SEE FIGURE 2 FOR WIRING EXTERNAL CTs 91 110 5 100 100 5 111 160 5 150 150 5 161 220 5 200 200 5 221 320 5 300 300 5 321 420 5 400 400 5 421 520 5 500 500 5 521 620 5 600 600 5 621...

Page 3: ...3 1 05 Figure 2 Typical Wiring Diagram Using External CTs Figure 3 Looping Example Showing Three Conductors MULT 3 from table 1 No other necessary connections are shown...

Page 4: ...efore the maximum deviation from the average is 5 3 The VUB is then 5 3 208 3 x 100 2 5 The TS setting allows the user to turn the temperature sensor trip function on or off MULT MULT multiplier setti...

Page 5: ...ck position to the 11 o clock position ADDR settings start after the 11 o clock position RU of restarts after an undercurrent is the number of restarts after an undercurrent trip condition before the...

Page 6: ...ntil all parameters are programmed OPERATION The relay operation of the Model 777 TS is designed to be fail safe This means when everything is within the limits programmed into the unit the relay will...

Page 7: ...15 Specialized applications 20 Standard Trip Most NEMA rated general purpose motors will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads...

Page 8: ...n e g worn bearings oc should not be included in the RF setting so that a manual reset after an overload fault is required A RF 1 will give the system 1 chance to recover from an unbalance or single p...

Page 9: ...ual line line voltage The display is also used for programming the operating parameters of the device The display also identifies what caused the unit to de energize its relay or what is keeping the u...

Page 10: ...vides isolation signal conditioning for compatibility with Modbus RTU and RS 485 networks and provides terminals for terminating the shielded communications cable Up to 99 units can be installed on on...

Page 11: ...meter value The incoming voltage is not within the limits programmed in the VUB HV and LV settings Adjust the DISPLAY PROGRAM switch to read the incoming line voltage values Correct the incoming power...

Page 12: ...irect Trip Times Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpoint 201 300 of Setpoint 301 400 of Setpoint 401 or Greater Trip time 8 seconds 1 second 4 second...

Page 13: ...C Undercurrent Threshold 0 10 98A MULT or 40 100 of CT Primary CUB Current Unbalance Threshold 2 25 or 999 TC Overcurrent Trip Class 5 J5 10 J10 15 J15 20 J20 30 J30 RD1 Rapid Cycle Timer 0 2 500 Seco...

Page 14: ...button 4 Turn MODE SELECT switch to RUN The program is now locked but all settings can be viewed The unit can be unlocked by following the same steps except adjust the DISPLAY PROGRAM knob to unL in...

Page 15: ...ng s electrical installation in order to be available to the authority having jurisdiction 9 Confirm programmed parameters and proceed with installation instructions GROUND FAULT TEST RESULTS Date Per...

Page 16: ...16 1 05 Visit our website at www symcominc com for our complete catalog and new product listings 2880 North Plaza Drive Rapid City SD 57702 800 843 8848...

Reviews: