PROGRAMMABLE OPERATING POINTS
LV- Low Voltage Threshold
85 V - HV Setting
HV - High Voltage Threshold
LV Setting - 264 V
VUB - Voltage Unbalance Threshold
2 - 15% or 999 (OFF)
MULT - CT Ratio (xxx:5)
25 - 600 Ratio
OC - Overcurrent Threshold
40 - 120% of CT Ratio
UC - Undercurrent Threshold
0, 20 - 100% of CT Primary
CUB - Current Unbalance Threshold
2 - 25% or 999 (OFF)
TC - Overcurrent Trip Class
**
5, J5, 10, J10, 15, J15, 20, J20, 30, J30, or J00
RD1 - Rapid Cycle Timer
0, 2 - 500 Minutes (x 0.5 if TC = J00)
MA - Motor Acceleration Timer
0 - 250 x (0.158 through 0.315) Seconds
RD2 - Motor Cool Down Timer
2 - 500 Minutes (x 0.5 if TC = J00)
OCTD - Overcurrent Trip Delay (Linear)
2-250 x (0.158 - 0.315) Seconds
RD3 - Dry Well Recovery Timer
2 - 500 Minutes (x 0.5 if TC = J00)
#RU - Number of Restarts After UC Fault
0, 1, 2, 3, 4, or A (Automatic)
ADDR - RS-485 Address
A01 - A99
#RF - Number of Restarts After All Faults
Except UC
***
0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, or ocA
UCTD - Undercurrent Trip Delay
2 - 60 Seconds
GF - Ground Fault Current Threshold
10 - 20% of CT Primary or OFF
-17-
06/26/03
NOTES: SymCom’s Overload Relay can be preprogrammed prior to installation by applying
120 VAC between the L1 and L2 terminals.
** If J Prefix is displayed in trip class setting, jam protection is enabled.
*** If “oc” is displayed in the #RF setting, then Over Current will be included as a
normal
fault and the relay will automatically restart after RD2 expires, otherwise, manual
reset is required after an Over Current fault.