background image

 

5 - 

 

6/07 A1

P will trip on overcurrent. While the standard trip classes are 5, 10, 15, 20, and 30, TC can 
be set from 2–30, with or without jam protection. These additional “non-standard” trip 
classes allow the unit to follow a trip curve in-between the “standard” trip class curves 
shown in Figure 4.  

 

Trip classes 2–30 can be set from approximately the 7 o’clock to 11 o’clock position on the 
DISPLAY/PROGRAM dial. Trip classes J02–J30, which include jam protection, can be set 
from the 11 o’clock to 2 o’clock position (this additional jam protection feature, when 
enabled is initiated 1 minute after the motor starts and provides a 2-second trip delay for 
motors exceeding 400% of the OC setting).  

 

The linear overcurrent trip delay can be set after the 2 o’clock position from 0–60 seconds 
(L00–L60) or to “oFF.” If TC is set to L00, the 777-P will trip off within 1 second when an 
overcurrent condition is detected. 

 

If both trip class and linear trip delay settings are programmed, the 777-P will follow the 
faster trip time. E.g., let’s say TC is set to J15 and L20, and the amperage is 200% of the 
OC setting. Following the trip class 15 curve, the 777-P will trip off in approximately 100 
seconds. Thus the 777-P will follow the linear trip delay setting, because it is faster, and will 
trip off in 20 seconds. 

 

The motor manufacturer should be contacted for an exact TC setting. Table 3 describes the 
trip classes, and Figure 4 shows the trip class curves. 

 
RD1 

-   RD1 (restart delay one) is the rapid-cycle timer in seconds. This timer is initiated when 

power is first applied to the unit. If voltages are within the programmed limits and no SP 
(single-phase) or RP (reverse-phase) condition exists when power is applied to the device, 
the output relay will energize (the NO will close and the NC will open) as soon as RD1 
expires. Typically, this is set to 20-30 seconds. This will provide adequate protection for 
successive power outages or short cycling caused by other motor controls. This timer is 
also initiated when another control shuts the motor off (current goes to zero). If the user 
does not want the unit’s relay to de-energize when another control shuts the motor off, then 
RD1 should be set to zero. This will also ensure that when an alarm circuit is used, an alarm 
will sound only when there is a fault or power is lost. 

 

RD2 

-   RD2 (restart delay two) is the restart timer, in minutes (standard), used when the unit has 

shut off due to a current unbalance, current single phasing, or an overload condition. This 
timer is known as a motor cool-down timer. A setting of 5-10 minutes will give most motors 
adequate time to cool down after an overload condition. The motor manufacturer should be 
contacted for an exact value. 

 

RD3- 

(restart delay three) is the restart timer, in minutes (standard), used after an undercurrent 
trip. It is also known as a dry-well recovery timer in pumping applications. This would be the 
time it takes a well to recharge after pumping dry. This setting varies widely from application 
to application and there is no typical setting. RD3 can be set from 2-500 minutes or to A to 
enable the automatic Dry-Well Recovery Calculator. 

 
 

The Automatic Dry-Well Recovery Calculator allows the 777-P to automatically select a 
restart delay based on the run time of the last run cycle. Table 2 shows the next restart 
delay vs. run time. In general, a longer run time produces a shorter restart delay. This 
feature allows the 777-P to optimize running and rest times automatically. 

 
 
 
 

 

Summary of Contents for MotorSaver Plus 777-575-P

Page 1: ...ps onto the rail 3 A For amperages from 25 90 amps insert the motor conductors through the holes marked A B and C Make certain the conductor through each hole corresponds to the right motor conductor...

Page 2: ...0 3 3 32 6 3 3 12 25 10 50 3 0 5 49 2 2 25 90 20 100 0 10 98 1 1 80 110 80 140 0 40 140 5 100 100 5 110 160 120 210 0 60 210 5 150 150 5 160 220 160 280 0 80 280 5 200 200 5 220 320 240 420 0 120 420...

Page 3: ...Figure 2 Typical Wiring Diagram Using External CTs Figure 3 Looping Example Showing Three Conductors MULT 3 from Table 1 3 6 07 A1 No other necessary connections are shown...

Page 4: ...7 210 208 3 1 7 and 208 3 203 5 3 The maximum deviation from the average is 5 3 thus voltage unbalance 5 3 208 3 x 100 2 5 MULT MULT multiplier setting is found on Table 1 The MULT setting is determi...

Page 5: ...hase or RP reverse phase condition exists when power is applied to the device the output relay will energize the NO will close and the NC will open as soon as RD1 expires Typically this is set to 20 3...

Page 6: ...only used when communicating with an RM 2000 RM 1000 COM DN CIO DN a PLC or a PC The address can be 1 99 A01 A99 RF RF is the number of restarts the 777 P will attempt after current unbalance or curre...

Page 7: ...played will be the number corresponding to where the DISPLAY PROGRAM knob is pointed It will do this for the amount of time programmed into RD1 After this time has expired the relay will energize NO c...

Page 8: ...will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads J Prefix Programming any of the trip classes with the J prefix will enable jam prote...

Page 9: ...RD3 does not have any function RF Because an overload overcurrent fault signals a serious problem in this application e g worn bearings oc should not be included in the RF setting so that a manual res...

Page 10: ...h line current or each individual line line voltage The display is also used for programming the operating parameters of the device The display also identifies what caused the unit to de energize its...

Page 11: ...tion signal conditioning for compatibility with Modbus RTU and RS 485 networks and provides terminals for terminating the shielded communications cable Up to 99 units can be installed on one RS 485 ne...

Page 12: ...rameter value The incoming voltage is not within the limits programmed in the VUB HV and LV settings Adjust the DISPLAY PROGRAM switch to read the incoming line voltage values Correct the incoming pow...

Page 13: ...rmer must be between 115 and 150 of the GF setting and pass through only one CT window 5 The values of V and R will be determined by the current required to generate a GF trip condition I Vrms R where...

Page 14: ...14 6 07 A1 GROUND FAULT TEST RESULTS Date Performed by Results Location A copy of this form should be retained by the building s electrical foreman...

Page 15: ...ge 0 5 of nominal voltage Current 1 100A direct Trip Times Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpoint 201 300 of Setpoint 301 400 of Setpoint 401 or Gre...

Page 16: ...0 10 98A MULT or 40 140 of CT Primary CUB Current Unbalance Threshold 2 25 or 999 disabled 02 30 J02 J30 TC Overcurrent Trip Class and Linear Overcurrent Trip Delay L00 L60 or oFF RD1 Rapid Cycle Tim...

Reviews: