Trip Class
Application Description
5
Small fractional horsepower motors where acceleration times are almost
instantaneous or where extremely quick trip times are required
10
(
Fast Trip) Hermetic refrigerant motors, compressors, submersible
pumps and general-purpose motors that reach rated speed in less than 4
seconds.
15
Specialized applications.
20
(Standard Trip) Most NEMA-rated general-purpose motors will be
protected by this setting.
30
(Slow Trip) Motors with long acceleration times (>10 seconds) or high
inertia loads.
J Prefix
Programming any of the trip classes with the J prefix will enable jam
protection. This additional protection is enabled 1 minute after the motor
starts and provides a 2 second trip time for motors exceeding 400% of
the OC setting, regardless of trip class.
LXX
This is linear overcurrent setting, where XX is the number of seconds for
a linear trip.
Other Trip
Classes
Trip Time in seconds at 6x OC=(TC*.93359s)
Table 3: Trip Class Descriptions
Figure 4: Overload Trip Curves
-