14 © 2010 SymCom, Inc. All Rights Reserved
CLEARING LAST FAULT/RESETTING PARAMETERS
The following steps will clear the last fault and reset all setpoints back to factory settings:
1. Rotate MODE SELECT to GF.
2. Press and hold the RESET/PROGRAM button. Adjust the DISPLAY/PROGRAM knob until “cLr”
appears on the display. Release the RESET/PROGRAM button.
To verify the last fault was cleared and that the parameters were reset to factory settings, place
MODE SELECT in the RUN position. Then press and hold the RESET/PROGRAM button; “cLr”
should be on the display.
TAMPER GUARD
The 777-P2-DEMO setpoints can be locked to protect against unauthorized program changes.
1. Rotate MODE SELECT to GF.
2. Press and hold the RESET/PROGRAM button. Adjust the DISPLAY/PROGRAM knob until “Loc”
appears on the display.
3. Release the RESET/PROGRAM button.
4. Turn MODE SELECT to RUN.
The program is now locked, but all settings can be viewed. The unit can be unlocked by following
the same steps except adjust the DISPLAY/PROGRAM knob to “unL” in step 2.