ACCESSORIES - CIO-EN-DEMO
If using the CIO-EN-DEMO communications module, connect the CIO-EN-DEMO to the side of a
777-P2-DEMO via the 9-pin D-SUB connector located on the side of the module. The CIO-EN-
DEMO will be powered on once connected to the 777-P2-DEMO. The CIO-EN-DEMO module is a
convenient Modbus/TCP and Modbus/RTU interface that provides a means of communicating with
the 777-P2-DEMO over a network or to a remote monitor display, such as the RM-1000-DEMO or
RM-2000-DEMO.
In order to communicate with an upstream device via a RS-485 network, the upstream device must
be connected to the CIO-EN-DEMO using a twisted-pair cable connected to A, B, and Shield of the
5-pin connector on the front of the CIO-EN-DEMO module. The CIO-EN-DEMO can be
programmed as device address A01-A99 and can communicate at baud rates of 9600, 19200,
38400, and 57600. The default communications settings for the CIO-EN-DEMO are:
• Baud Rate: 19200
• Parity: Even
• Modbus Address: Flexible when attached to 777-P2-DEMO
• When using SymCom
Solutions
, open
Solutions
and click ‘Modbus/RTU’ in the Select Network
Connection Type Box. Ensure the network communication settings are correct, and the device
connections are correct. Right click in the network window and select ‘Manually Add a Unit’.
Select the 777-P2 model and press ‘Enter’. Click on the unit to view its properties.
In order to communicate with SymCom
Solutions
via a Modbus/TCP network, connect an Ethernet
cable to the Ethernet jack on the top of the CIO-EN-DEMO and to the PC (Ethernet cable included
with CIO-EN-DEMO). The default Ethernet communications settings for the CIO-EN-DEMO are:
• IP Address: 192.168.50.FLEX where FLEX = 777-P2-DEMO Modbus Address
• Subnet Mask: 255.255.0.0
• Gateway: 192.168.50.1
• DHCP: Disabled
• When using SymCom
Solutions
,
open
Solutions
and click ‘Modbus/TCP’ in the ‘Select
Network Connection Type’ option menu. Ensure the Ethernet network communication settings
are correct, and the device connections are correct. Right click in the network window and
select ‘Manually Add a Unit’. Select the 777-P2 model and press Enter. Click on the unit to
view its properties.