098-00028-000 Revision F – May, 2012
TimeProvider 5000 User’s Guide 313
Chapter 4 Provisioning
Provisioning the Input Reference
8. Type
set input priority port2 6
and press
Enter
.
9. Type
show ref
and press
Enter
to verify that Priority values have been set to
the desired values.
Setting GPS Port as Reference
When the GPS reference is enabled, you can set the satellite position parameters
either automatically or manually. The GPS reference input is enabled by default. In
manual mode, you must specify the latitude, longitude, and height. You can also
specify the elevation mask which filters the satellites used by the system.
Table 4-15. Reference Modes and Priorities
Input Port
Card
Ref. Type
Reference
Criteria
Priority
(Default)
Predefined
Preference
PQL
(Default)
GNSS
IMC
Time
Priority
1
1
1
GPS
IMC
Time
Priority
2
2
1
1PPS+TOD
Port 1
I/O
Time
Priority
3
3
1
1PPS+TOD
Port 2
I/O
Time
Priority
4
4
1
E1 / T1
Port 1
I/O
Frequency
Priority
7
7
3
E1 / T1
Port 2
I/O
Frequency
Priority
8
8
3
Note:
Manual mode should not be used unless antenna location has
been accurately surveyed. See the
command description for
for details about setting GPS position parameters manually.
Summary of Contents for TimeProvider 5000
Page 12: ...Table of Contents 12 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 16: ...List of Figures 16 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 20: ...List of Tables 20 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 56: ...56 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 Chapter 1 Overview Alarms ...
Page 534: ...Index W W 534 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...