Provisioning the Input Reference
To provision the TimeProvider 5000 for a GNSS reference in auto mode, with a
track-mode of Priority-beidou, perform the following steps:
1. Login at the Admin or Config-user level (see
2. Type
set ref mode time
and press
Enter
.
3. Type
set gnss mode auto
and press
Enter
.
4. Type
set gnss track-mode priority-beidou
and press
Enter
.
5. Type
set gnss state enable
and press
Enter
.
6. Type
show ref
and press
Enter
to verify that the reference mode has been set
to Time.
Setting a 1PPS+TOD Input as Reference
Ports 1 and 2 on the 090-50315-01 version of the I/O module are 1PPS+TOD
inputs. Use the following procedure to set these ports as reference inputs and to
enable the inputs.
Example
To provision the TimeProvider 5000 for a 1PPS+TOD input reference, perform the
following steps:
1. Login at the Admin or Config-user level.
2. Type
set ref mode time
and press
Enter
3. Type
set pps-tod state port1 enable
and press
Enter
.
4. Type
set pps-tod state port2 enable
and press
Enter
.
5. Type
show ref
and press
Enter
to verify that the reference mode has been set
to Time.
Note:
Disabling the input port will clear all alarms and events related
to this port.
Note:
Command “
set ref mode time”
has the same meaning as
“
set tod-source GPS”
and “
set ref mode frequency”
has
the same meaning as “
set tod-source sys”
. The
command has been deprecated.
Summary of Contents for TimeProvider 5000
Page 12: ...Table of Contents 12 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 16: ...List of Figures 16 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 20: ...List of Tables 20 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 56: ...56 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 Chapter 1 Overview Alarms ...
Page 534: ...Index W W 534 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...