098-00028-000 Revision F – May, 2012
TimeProvider 5000 User’s Guide 331
Chapter 4 Provisioning
Provisioning the Dedicated Outputs
6. Type
set output state port4 enable
and press
Enter
.
CAS Frame Type
To provision output Port 4 with a frametype of CAS, CRC enabled, SSM-bit of 8, and
to enable the port:
1. Login at the Admin or Config-user level.
2. Type
set output frametype port4 cas
and press
Enter
.
3. Type
set output crc port4 enable
and press
Enter
.
4. Type
set output ssm port4 enable
and press
Enter
.
5. Type
set output ssm-bit port4 8
and press
Enter
.
6. Type
set output state port4 enable
and press
Enter
.
Provisioning Output Generation Behavior
The behavior of the dedicated output ports during warm-up, free-run, fast-track and
holdover states can be provisioned using the “set output warm-up”, “set output
free-run”, “set output fast-track” and “set output holdover” commands, as shown in
.
1. Login at the Admin or Config-user level.
2. Type
set output warm-up port4 squelch
and press
Enter
.
3. Type
set output free-run port4 on
and press
Enter
.
4. Type
set output holdover port4 on
and press
Enter
.
5. Type
set output fast-track port4 squelch
and press
Enter
.
Summary of Contents for TimeProvider 5000
Page 12: ...Table of Contents 12 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 16: ...List of Figures 16 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 20: ...List of Tables 20 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 56: ...56 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 Chapter 1 Overview Alarms ...
Page 534: ...Index W W 534 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...