098-00028-000 Revision F – May, 2012
TimeProvider 5000 User’s Guide 411
Appendix A System Messages
System Notification Messages
Internal
communication
error
(See
for
Secondary Index Info)
IOC
19
Critical
No
Internal
communication error
Internal
communication error
cleared
Reboot System - If
alarm remains,
replace module
None required
FPGA temperature
exceed limit
IOC1
IOC2
EXPx
x
= 0
9
20
Minor
No
FPGA temperature
exceed limit
FPGA temperature
exceed limit cleared
Check room
temperature setting.
None required
IOC detected but
none of them active
IMC
21
Major
No
IOC detected but
none of them active
Active IOC detected
Reboot system
None required
Module reboot
IMC
IOC1
IOC2
EXPx
x
= 0
9
22
Event
Yes
Module reboot
None required
Real Time Engine
(RTE)
communication to
peer error
IOC
23
Major
No
RTE communication
to peer error
RTE communication
to peer error cleared
Reboot System - If
alarm remains,
replace IOC module
None required
Entered warmup
mode
IOC1
IOC2
EXPx
x
= 0
9
24
Minor
No
Entered warmup
mode
Transitioned out of
warmup mode
None required - If
still present after 30
min. check other
system alarms
None required
Entered freerun
mode
IOC1
IOC2
EXPx
x
= 0
9
25
Event
No
Entered freerun
mode
Transitioned out of
freerun mode
If freerun mode not
desired, check
system input
reference
None required
Table A-1. System Notification Messages (Continued)
Description
Comp
ID
Event
ID
MsgLevel
Trans-
itory
MsgText
Corrective Action
Summary of Contents for TimeProvider 5000
Page 12: ...Table of Contents 12 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 16: ...List of Figures 16 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 20: ...List of Tables 20 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 56: ...56 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 Chapter 1 Overview Alarms ...
Page 534: ...Index W W 534 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...