F73 – Alarm Control / Status
To display the latched faults, enter:
F73 LATCH
The XL-GPS responds in the following format:
F73<SP>LATCH<SEP><123456789ABCDE><CR><LF>
The values in <123456789ABCDE> field indicate the latched faults, if any, which have
occurred since the last time Alarm Latch was cleared.
To clear the Alarm Latch, enter:
F73 CLEAR ALARM LATCH<CR><LF>
The XL-GPS clears Alarm Latches and responds:
OK<CR><LF>
The user can enable or disable the alarm indicators using the MASK command. To display
the current mask, enter:
F73 MASK
The XL-GPS responds in the following format:
F73<SP>MASK<SEP><123456789ABCDEFGHIJ><CR><LF>
Where the value of each character in <123456789ABCDEFGHIJ> field is either 'E' or 'D'. 'E'
means the corresponding indicator is enabled, and can trigger an alarm if it enters a fault
state. 'D' means the indicator is disabled (or not available) and will not trigger an alarm if it
enters a fault state.
To enable ('E'), disable (‘D’), or leave the indicator unchanged (‘-’), enter 'E', 'D', or '-' for
each character in <123456789ABCDEFGHIJ> when you enter the following string:
F73<SP>MASK<SEP><123456789ABCDEFGHIJ><CR>
The XL-GPS will sets the new alarm mask and responds:
OK<CR><LF>
The following summarizes the fault alarm mask setting in the <123456789ABCDEFGHIJ>
field:
1
=
'E
' PLL Synthesizer Alarm Enabled
098-00116-000 Rev. A
...............................
Page 101 of 221
Summary of Contents for XL-GPS
Page 1: ...XL GPS Time Frequency Receiver User Guide CD Part Number 098 00116 000 Rev A 5 May 2010 ...
Page 14: ......
Page 34: ......
Page 50: ......
Page 196: ......
Page 214: ...IRIG IRIG Standard Format A 098 00116 000 Rev A Page 200 of 221 ...
Page 215: ......
Page 216: ...F World Map of Time Zones 098 00116 000 Rev A Page 202 of 221 ...
Page 219: ......
Page 220: ...I Certificate of Volatility See the following document 098 00116 000 Rev A Page 206 of 221 ...
Page 224: ......
Page 225: ...J Declaration of Conformity See the following document 098 00116 000 Rev A Page 208 of 221 ...