Ensure that the ambient operating temperature does not 50
°
C. Install the
XL-GPS chassis so that the top and bottom holes are unobstructed and have sufficient
clearance to allow 5 cfm of air to pass through the chassis. To maintain recommended
operating temperatures, install a rack-cooling fan capable of 100 cfm in heavily loaded racks.
Grounding
WARNING:
Chassis Grounding Screw
Symmetricom recommends that the user connect the chassis grounding screw to a reliable
earth ground.
AVERTISSEMENT:
Symmetricom recommande que le châssis soit relié à une terre fia-
ble.
Proper Grounding
Maintain reliable grounding (earthing) of rack-mounted equipment.
The ground screw provided with the XL-GPS instrument, is a stainless steel, pan head, 10-
32, 0.375 inch long, machine screw.
Grounding the XL-GPS
l
For VAC power, verify that a properly grounded three-prong outlet is available for
the standard power cord.
l
Connect the Chassis Grounding Screw on the rear panel to a reliable earth ground.
l
Verify that the equipment rack and other equipment are grounded correctly.
Page 34 of 221
.................................
098-00116-000 Rev. A
Summary of Contents for XL-GPS
Page 1: ...XL GPS Time Frequency Receiver User Guide CD Part Number 098 00116 000 Rev A 5 May 2010 ...
Page 14: ......
Page 34: ......
Page 50: ......
Page 196: ......
Page 214: ...IRIG IRIG Standard Format A 098 00116 000 Rev A Page 200 of 221 ...
Page 215: ......
Page 216: ...F World Map of Time Zones 098 00116 000 Rev A Page 202 of 221 ...
Page 219: ......
Page 220: ...I Certificate of Volatility See the following document 098 00116 000 Rev A Page 206 of 221 ...
Page 224: ......
Page 225: ...J Declaration of Conformity See the following document 098 00116 000 Rev A Page 208 of 221 ...