Rinnai Australia
31
Installation Manual
FLUE INSTALLATION CONFIGURATION
TYPES OF FLUE INSTALLATION
The types of suitable flue configurations are shown above. Other flue configurations are not suitable. Suitable flue
components are shown below. Other flue components not shown are not suitable. For full details regarding flue
assembly and installation refer to the ‘Simpson Duravent’® “DirectVent Pro” Installation Instructions supplied with
the flue components.
A ‘flue restrictor plate’ needs to be installed inside the appliance for some flue configurations. This is to ensure the
correct amount of ‘natural draft’ can be achieved. Refer to the section “CONNECT FLUE AND INSTALLING THE
FLUE RESTRICTOR” on page 35 for more information.
FLUE TERMINAL LOCATION
The flue terminal should be positioned away from flammable
materials.
Ensure that the location of the flue terminal can comply with the
requirements of AS/NZS 5601, Fig. 6.2 which is reproduced below.
Clearances for Natural Draft apply.
* AS/NZS 5601 was current at the time of printing this manual, but may have been
superseded. It is the installers responsibility to ensure that the current version of this
standard is used.
WARNING
Natural draf t Fan assisted
• Appliances
0
0
2
0
0
3
t
u
p
n
i
h
/
J
M
0
5
o
t
p
u
• Appliances
0
0
3
0
0
5
t
u
p
n
i
h
/
J
M
0
5
r
e
v
o
0
0
3
0
0
3
*
e
c
a
fr
u
s
r
e
h
t
o
r
o
y
n
o
c
l
a
b
a
e
v
o
b
a
,
d
n
u
o
r
g
e
h
t
m
o
r
F
b
0
0
3
0
0
5
*
r
e
n
r
o
c
l
a
n
r
e
t
x
e
r
o
ll
a
w
n
r
u
t
e
r
a
t
n
o
r
F
c
d
From a gas meter (M) (see 5.11.5.9 for vent terminal location of regulator )
0
0
0
1
0
0
0
1
)
s
t
n
e
m
e
ri
u
q
e
r
d
n
a
l
a
e
Z
w
e
N
r
o
f
6
.
6
e
l
b
a
T
e
e
s
(
e
From an electricity meter
0
0
5
0
0
5
†
)
P
(
x
o
b
e
s
u
f
r
o
5
7
0
5
1
e
p
i
p
li
o
s
r
o
e
p
i
p
n
i
a
r
d
a
m
o
r
F
f
g
Horizontally from any building structure* = or obstruction facing a termina l
500
500
h
From any other flue terminal , cowl, or combustion air intake †
500
300
• Appliances
0
0
3
0
0
5
*
t
u
p
n
i
h
/
J
M
0
5
1
o
t
p
u
• Appliances over 150 MJ/h input up to 200 MJ/h input *
1500
300
• Appliances over 200 MJ/h input up to 250 MJ/h input *
1500
500
• Appliances
0
0
5
1
0
0
5
1
*
t
u
p
n
i
h
/
J
M
0
5
2
r
e
v
o
• All fan-assisted flue appliances , in the direction of discharg e
-
1500
0
0
0
1
0
0
5
1
r
e
w
o
l
b
a
p
s
a
g
n
i
d
u
l
c
n
i
,t
e
l
n
i
ri
a
l
a
c
i
n
a
h
c
e
m
a
m
o
r
F
k
0
5
1
0
5
1
t
u
p
n
i
r
h
/
J
M
0
5
o
t
p
u
s
r
e
t
a
e
h
e
c
a
p
S
•
• Other appliances
0
0
5
0
0
5
t
u
p
n
i
r
h
/
J
M
0
5
o
t
p
u
• Appliances over 50 MJ/h input and up to 150 MJ/h inpu t
1000
1000
• Appliances
0
0
5
1
0
0
5
1
t
u
p
n
i
h
/
J
M
0
5
1
r
e
v
o
1
Where dimensions c, j or k cannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2
See Clause 6.9.4 for restrictions on a flue terminal under a covered area.
3
See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder.
A flue terminal is considered to be a source of ignition.
4
m
e
tI
.f
e
R
a
Min. clearances (mm)
Below eaves, balconies and other projections:
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building
with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a building with the
exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.
FIGURE 6.2
(in-part) MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS, FAN-ASSISTED
FLUE TERMINALS, ROOM-SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless appliance is certified for closer installation
For appliance s not addressed above acceptance should be obtained from the Technical Regulator.
n
Flue terminal
Fan assisted flue appliance only
Gas meter
Electricity meter or fuse box
Mechanical air inlet
NOTE