■ Connect 1
20 VAC
line voltage to the primary side of the
transformer as displayed in Figure 1.
12V
6V
T
coil
connections
Relay 12 VDC @ <80mA
(customer supplied option)
Remote monitoring
system connections
Temperature probe and
1/4" NPT male fitting
Water hammer
arrestor (optional)
Tee fitting
(required, see
options)
Alarm
control
module
Water flow
Transformer
12 VAC/15 VA
Solenoid valve (optional)
12 VDC, 10 Watts max
120 VAC Power
25'probe cable
(optional lengths)
■ Connect the
12 VAC
secondary side of the transformer to
the
12 VAC power input
terminals on the back of the alarm
control module as identified in Figure 2 below. Note that
there is no polarity required for the input terminals.
ON
OFF
Fuses #229
1.5A / 250VP
12 VAC
power input
12 VDC valve
power output
(optional)
Temperature
input probe
DIP Switches
Rear view of Alarm Control Module
12 VDC relay
power output
(optional)
■
Temperature Probe
- Plug probe into the connector on
the backside of the control module as identified in Figure 2
above. Note that the connectors are keyed and will only mate
in one direction. (optional cable lengths are available)
■
Solenoid Valve
(optional)
-
Connect coil wires between the
solenoid valve and the
valve power output terminals
on the
back of the control module as identified in Figure 2 above.
Note that there is no polarity required between connections.
High Temperature Audio Visual Alarm System,
HTA-100
Installation and Service Instructions
TempControl
®
General Information
■
Alarm System
- TempControl High Temperature Audio
Visual Alarm System will monitor, alert and alarm when
water temperature exceeds preset limit. It best fits
applications where there is a critical need to accurately
monitor and control warm or hot water temperature.
■
Solenoid Valve
(optional) - When alarmed, the valve is
de-energized and closes to provide complete shutdown of
the water flow.
■
Relay
(customer supplied option) - Installed relay enables
remote monitoring of alarm control module.
■
Caution Set Point
- is the lower of the two set point
temperatures that alerts when the output water is
approaching an undesirable temperature limit.
■
Alarm Set Point
- Once the output temperature reaches the
alarm set point
, the system goes into full alarm mode.
Installation
Important:
All piping should be thoroughly
flushed prior to installation to prevent debris from
interfering with the solenoid operation.
Do not
run
solenoid power and temperature probe through
same conduit.
Piping
■
Tee Fitting -
Required; appropriate size fitting for
application purchased seperately (see options).
■
Temperature Probe -
Locate probe as far downstream from
mixing valve as is reasonably possible.
a. Slide connector nut and ferrule piece over the probe.
b. Slide probe
1/2”
to
2/3”
into the tee fitting.
c. Slide the ferrule and connector nut down the probe shaft
and tighten in place.
■
Solenoid Valve
(optional, 12 VDC, 10 Watts
, normally
closed) - Install valve directly before the temperature probe in
any orientation. Make note of the correct direction of the water
flow as marked on the valve.
Electrical
■ Mount the
4" x 4
" supplied mounting box in a dry location
within wiring reach of the temperature probe and solenoid
valve if used.
■ Mount supplied transformer.
(
120 VAC – 12 VAC/15 VA UL listed, CSA certified class 2)
Figure 1
Figure 2