User’s Manual
Synaccess Networks, Inc.
www.synaccess-net.com
(760) 930 – 0473 Page 19 of 46
Event Notifications
lastTrapMessage
.100.1.1
Explicit operation events. Last TRAP/Notification sent. The messages
include outlet power status changes, AutoPing/Reboot events, system
power on event, user login/logout event, ..."
CurrentThresholdCross-Event
.100.1.2
Current draw (Amps) crosses the defined threshold for inlet 1 or 2."
temperatureThresholdCrossEvent
.100.1.3
Environment temperature reading (in F) crosses predefined threshold.
Figure 12 - List of MIB object
3.9 AutoPing and Power Reboot:
Each power outlet has optional settings that a NP system uses to ping network equipment. The
pinged equipment is attached to a specific power outlet. It reboots user equipment power source if a
network connection is not detected any more. However, user equipment never gets power reboot if
the equipment never replies ping reply to a NP system.
A power outlet has the optional settings (Power Outlet Setup Menu) that specify the destination IP
address that the system will ping periodically, and maximum network downtime allowed. In
addition, to avoid unwanted reboots, a NP system also pings the gateway IP address (as default) to
make sure a NP system has a network connection that is still active. Otherwise, AutoPing will be in
off mode if a NP system lost network connection. To change the default gateway IP address as ping
destination, use TCP/IP Configuration Menu to enter your desired destination address.