DOC-1000496-A-1
SPECIFICATIONS
•
Relay Max Switch Circuit:
o
5A @ 110-277VAC (+/- 10%)
o
3A @ 347VAC (+/- 10%)
o
2A @ 480VAC (+/- 10%)
•
Dim Control Max Load: 20mA
•
Radio Frequency: 2.4 GHz (IEEE 802.15.4)
•
RF Transmission Output Power: +20dBM
•
Operating Temperature: -40 to +70 C
•
Operating Humidity: 0 to 90%, non-condensing
•
Dimensions: 3.3” D x 3.9” H
(84mm D x 98mm H)
•
Surge Protection: 6kV
•
Sensor Input: 24V
•
Sensor Power Max Load: 24VDC @ 20mA
CAUTION
•
This product must be installed in accordance with
national, state, and local electrical codes and
requirements
•
All work must be performed by qualified personnel
•
Disconnect all power before installation or service
WIRING DETAILS OF C136.41 SOCKET
WARNING: TO AVOID FIRE, SHOCK, OR DEATH:
TURN OFF POWER
AT CIRCUIT BREAKER OR FUSE
AND VERIFY THAT POWER IS OFF BEFORE WIRING!
If a motion sensor or the C136.41 socket needs to be
wired up prior to installing the TL7-HVG, please refer
to the wiring details.
(See Figure 1)
WARNING AND CAUTIONS:
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER
AT CIRCUIT BREAKER OR
FUSE AND TEST THAT POWER IS OFF BEFORE INSTALLING!
•
The TL7-HVG should only be installed in a fixture with a NEMA/ANSI C136.41 receptacle.
•
Device is rated up to 6kV surge, take steps to install an external surge protector for
additional protection.
•
Failure to follow these instructions and warnings could potentially void warranty.
TL7-HVG Lighting Controller
Load Rating: 110-480VAC ±10%
WARNING AND CAUTIONS:
•
To be installed and/or used in accordance with appropriate electrical codes and
regulations.
•
If you are unsure about any part of these instructions, consult an electrician; all work
should be performed by qualified personnel.
•
Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture
or changing lamps.
INSTALLATION GUIDE
Figure 1 – C136-41 Socket Wiring Details